Service Manual 47
Part 4 Trouble Shooting
■ 18,24,30kBtu/h Model
Indoor Error
00
No Error
ON
01
Indoor Room themistor error
1time
OFF
02
Indoor in-piping sensor error
2times
OFF
03
Remote controler error
3times
OFF
04
Drain Pump error
4times
OFF
05
Communcation error between in and out
5times
OFF
06
Indoor Out-Piping sensor error
6times
OFF
07
Diffrent mode operation
times
OFF
Outdoor Error
Ex) Error Code 21 (IPM Fault)
1 Time
1 Time
1 Time
2 Times
2 Times
2 Times
1 Sec.
2 Sec.
2 Sec.
1 Sec.
1 Sec.
LED01G
(RED)
LED02G
(GREEN)
Case of error
LED02G
(Green)
LED01G
(Red)
Contents
Error
code
Compressor malfunction,IPM Fault
Current is 14A
DC Link volt. Is 140V
Low / High press switch OPEN
Abnormal AC volt. Input.
Off
Off
Off
IPM Fault (Compressor Over current)
CT 2(Max. Current)
DC Link Low Volt.
Low / High press
AC Low / AC High Volt.
DC Compressor Position
PSC Fault
DC Link High Volt
Discharge Pipe Temp. High (INV)
Discharge Pipe Temp. High (Cons.)
21
22
23
24
25
26
27
28
32
33
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Outdoor
Status
2 times
2 times
2 times
2 times
2 times
2 times
2 times
2 times
3 times
3 times
1 time
2 times
3 times
4 times
5 times
6 times
7 times
8 times
2 times
3 times
Error code
Descrition
INV TPS
LED1
LED2
Indoor
(Red)
(Green)
Status