Notice – LG General Wall Mounted-Inverter Type User Manual
Page 40

40 Room Air Conditioner
Part 4 Trouble Shooting
2. Check temperature and pressure of refrigeration cycle.
1. The suction pressure is usually 8.5~9.5 kg/cm
2
.g at normal condition.
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with
putty.
NOTICE
Suction pressure
Temperature
(Compared with
(Compared with
Cause of Trouble
Description
the normal value)
the normal value)
High
Defective compressor
Current is low.
Normal
Excessive amount of
High pressure does not quickly
refrigerant
rise at the beginning of operation.
Insufficient amount of
Current is low.
Lower
Higher
refrigerant(Leakage)
Clogging
Higher
See also other documents in the category LG Conditioners:
- ARNU07GSEL1 (14 pages)
- AMNH12GTRA0 (39 pages)
- UT18H.NPD (304 pages)
- ARNU07GB1G1 (15 pages)
- ARNU18GS3M2 (205 pages)
- ARNU07GSEL2 (205 pages)
- ARNU07GTEC2.ENWALEU (205 pages)
- ARNU15GBHA2 (193 pages)
- ARNU24GCFU2 (205 pages)
- ARNU07GSFE2 (239 pages)
- ARNU09GSF11 (17 pages)
- AS-W2438*H0 (9 pages)
- LW1800PR (50 pages)
- Air Conditioner (28 pages)
- LT121CSG (39 pages)
- Floor Standing Type Air Conditioner (30 pages)
- LA120HPI (76 pages)
- LS090CP(AS-C0914DH0) (80 pages)
- LA121CPMO (71 pages)
- HB1004R (40 pages)
- L1404R (27 pages)
- EN 61000-2 (29 pages)
- 3828A22005P (27 pages)
- Air Conditioner LW701 HR (44 pages)
- LT1230C (23 pages)
- LSN180CE (83 pages)
- LB1200ER (28 pages)
- LT1230HR (34 pages)
- LW1404ER (27 pages)
- WG2405RY6 (42 pages)
- LA120CP (76 pages)
- LA090CP (36 pages)
- 11,800 BTU Thru-the-Wall Air Conditioner Use & Care Guide (48 pages)
- 11,800 BTU Thru-the-Wall Air Conditioner Use & Care Guide (48 pages)
- 230/208V (35 pages)
- 3828A30087S (33 pages)
- LP 1200DXR (26 pages)
- LT1030HR (48 pages)
- LS122CE (31 pages)
- 6710 YS (19 pages)
- LP091CEM-Y8 (48 pages)
- LP121HEM-Y8 (47 pages)
- AMNC123APM0 (86 pages)
- LM50 2004-E1 (78 pages)
- LS305HV (31 pages)