Troubleshooting – Lochinvar Armor 150 - 500 User Manual

Page 31

background image

Service Manual

31

3

Troubleshooting

(continued)

Table 3E (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Water Heater Interface

FAULT

DESCRIPTION

CORRECTIVE ACTION

Service Blk

While the unit is in Service Mode, the outlet
temperature has exceeded 185°F.

• Establish a heating load to remove the heat from the

water heater loop.

• Verify that the system is full of water and that all air

has been properly purged from the system.

• Verify that the water heater is piped properly into the

heating system. Refer to Section 6 - System Piping
of the Armor Water Heater Installation and Operation
Manual for the proper piping methods for the Armor
water heater.

• Check 120 VAC to the water heater pump motor on a

call for heat. If voltage is not present, check the wiring
back to the main control board. Replace the main
control board if necessary.

• If 120 VAC is present on a call for heat and the water

heater pump is not operating, replace the pump.

• Verify that the water heater pump is set to the proper

speed or that the water heater pump is the proper
size. Reference Section 6 - System Piping of the
Armor Water Heater Installation and Operation
Manual for water heater pump specifications.

Low 24 VAC

120 VAC input to the main control board has
dropped below 80 VAC.

• Check 120 VAC supply to the transformer.

• Check wiring connections at the low voltage terminal

strip.

• Check the wire size/length to remote devices.

• Replace the transformer.

Watch Dog Error

The main control board has detected an
internal fault.

• Replace the main control board.

Write EEProm

The main control board has detected an
internal fault.

• Replace the main control board.

CRC Parameters

The main control board has detected an
internal fault.

• Replace the main control board.

No Error Stored

The main control board has detected an
internal fault.

• Replace the main control board.