Troubleshooting – Lochinvar Armor 150 - 500 User Manual

Page 24

background image

3

Troubleshooting

24

Service Manual

Table 3D Troubleshooting Chart - Noisy System

FAULT

CAUSE

CORRECTIVE ACTION

Noisy

Operation

- Supply gas problem. Natural gas pressures

should be between 4 inches w.c. and
14 inches w.c. LP gas pressures should
be between 8 inches w.c. and
14 inches w.c.

• Refer to Section 7 - Gas Connections of the Armor

Water Heater Installation and Operation Manual for
detailed information concerning the gas supply.

- Gas/air mixture problem.

• Refer to the Gas Valve Adjustment Procedure on

page 33 of this manual for the proper gas valve setting.
Verify that the vent/air intake lengths do not exceed the
maximum listed in the General Venting section of the
Armor Water Heater Installation and Operation Manual.

- Dirty/damaged burner.

• Refer to page 19 in this manual for the burner removal

and inspection procedure. Clean or replace the burner
as necessary.

- Low water flow through the heat exchanger.

• Refer to Section 6 - System Piping of the Armor Water

Heater Installation and Operation Manual for minimum
flow rates.

- Air in the piping system.

• Properly purge all air from the piping system.

- Low system water pressure.

• Verify system pressure is a minimum of 12 PSI.

No Pump

Operation

- Blown fuse.

• Replace fuse F5 on the control board, see page 21 of

this manual.

- Faulty pump.

• Replace pump.

- Faulty pump relay.

• Replace pump relay.

- Internal fault on control board.

• Replace main control board.

Relief Valve

Opening

- System pressure exceeds relief valve

setting.

• Lower the system pressure below the 150 PSI rating of

the supplied relief valve.

APS

Open

(will require a

manual reset once the

condition has been

corrected. Press the

RESET button on the

SMART SYSTEM

display to reset.)

Air pressure switch contacts are open.

• Check the wiring connections to switch. Wires should

be connected to the common and normally closed
terminals.

• Air intake lengths exceed the maximum allowed

lengths. Refer to Section 3 - General Venting of the
Armor Water Heater Installation and Operation Manual
for proper lengths.

• Check for obstruction or blockage in the air

intake pipes or at terminations.

• Check reference hoses connected to the air pressure

switch for blockage or obstruction.

• Inspect the burner. Reference page 19 of this manual

for removal and cleaning procedures. Replace if
necessary.

• Inspect the heat exchanger. Reference page 20 of this

manual for removal and cleaning procedures. Replace
if necessary.

• Faulty air pressure switch. Replace switch.