Relief Valve
This water heater is supplied with
temperature and pressure relief valve(s)
sized in accordance with ASME Boiler and
Pressure Vessel Code, Section IV “Heating
Boilers.”

ELECTRICAL REQUIREMENTS

(North America)

The appliance is wired for 120 volts.

All wiring between the unit and field
installed devices shall be made of type
T wire [63°F (35°C) rise].

The pump must be wired to run
continuously when unit is firing.

It is recommended that the water heater
and pump be wired on separate circuits
with properly sized breakers.

Lochinvar

NOTE:

When the unit is

installed in Canada, it

must conform to the

CAE C22.1, Canadian

Electrical Code, Part 1,

and/or local Electrical

Codes.

NOTE:

Incorrect piping

of the cold water

supply to the

system will result

in condensate formation

on the heat exchanger

and operational

problems. Higher water

temperatures reduce

condensate formation.

Refer to drawings in

Appendix A.

(TABLE H) – COMMON WATER MANIFOLD

SIZE FOR MULTIPLE WATER HEATER

INSTALLATION

Pipe sizing chart provides minimum pipe size for

common manifold piping to ensure adequate flow.

NUMBER OF

COMMON MANIFOLD SIZE

UNITS

(Min.)

CW 495 thru 745

1

2

2

3

3

3

1

/

2

4

4

5

5

6

5

CW 986 thru 2066

1

2

1

/

2

2

4

3

4

4

5

5

6

6

6

2.

1.

3.

(TABLE I) – AMP DRAW DATA

MODEL

FAN(S)

CONTROLS

PUMP

TOTAL AMPS

NUMBER

w/PUMP

CW 495-745

3.4

4.6

5.8

13.8

CW 986-1256

3.4

4.6

7.4

15.4

CW 1436-2066

3.8

4.6

7.4

15.8