For this type of installation, it is best to use a
draft control for each water heater located
on the riser between the vent outlet and the
breeching - Location “A”. When this riser is
too short to permit the installation of a draft
control, locate a separate control for each
water heater on the main breeching as
illustrated in Location “B”. If, because of
general crowding or other reasons, neither
of these locations are possible, use a single
large control in the breeching between the
water heater nearest the chimney and the
chimney, as shown in Location “C”.

All draft readings are made while unit is in
stable operation (approximately 5 minutes
running time).

Masonry Chimney
A masonry chimney must be properly sized
for the installation of a high efficiency gas
fired appliance. Exterior masonry chimneys,
with one or more sides exposed to cold
outdoor temperatures, are more likely to
have venting problems. The temperature of
the flue products from a high efficiency
appliance may not be able to sufficiently
heat the masonry structure of the chimney to
generate proper draft. This will result in

condensing of flue products, damage of the
masonry flue/tile, insufficient draft and
possible spillage of flue products into an
occupied living space.

Carefully inspect all chimney systems during
the project design phase. If there is any doubt
about the sizing or condition of a masonry
chimney, it is prudent to reline the chimney
with a properly sized and approved chimney
liner system. Metallic liner systems (Type “B”
doublewall or flexible or rigid metallic liners)
are recommended. Consult with local code
officials to determine code requirements or the
advisability of using or relining a masonry
chimney.

OUTDOOR INSTALLATION

Units are self venting and can be used
outdoors when installed with the optional
Outdoor Cap. This cap mounts directly to
the top of the water heater and covers the
flue outlet and combustion air inlet openings
on the jacket. No additional vent piping is
required. Maintain a minimum clearance of
3

” (76 mm) to combustible surfaces and a

minimum of 3

” (76 mm) clearance to the air

inlet.

L o c h i n v a r

D E S I G N E R

S

G U I D E

C O P P E R

-

F I N

W A T E R

H E A T E R

6 1 5 - 8 8 9 - 8 9 0 0

9

NOTE:

Common venting

systems may be too

large when an existing

unit is removed. Be

careful to resize any

common venting system

when new appliances

are installed or existing

appliances are replaced.

NOTE:

Flue gases will form a

white plume in winter.

Plume could obstruct

window view. Flue gas

condensate can freeze

on exterior surfaces or

on the vent cap. Flue

gas condensate can

cause discoloration of

exterior building

surfaces. Adjacent brick

or masonry surfaces

should be protected with

a rust resistant sheet

metal plate.

(FIG. 8) MULTIPLE UNIT BAROMETRIC

DAMPER INSTALLATION

(FIG. 9) OUTDOOR VENTING

NOTE:

Venting of a high

efficiency appliance into

a cold or oversized

masonry chimney can

result in operational and

safety problems.