beautypg.com

Pump, Pump-rec-05, Recommendation – Lochinvar PUMP-REC-05 REV B User Manual

Page 2: Pump specifications, Installation specifications

background image



PUMP-Rec-05

PUMP

Recommendation

PUMP RECOMMENDATION FOR

COPPER-FIN 0986-2066 WATER HEATER

Pump Specifications

Part No.

HorsePower

Flanges

Valute Material

Flange Material

Vendor

Vendor Product Series

Orientation

ARM3024PAB 1/2 2-1/2" Brass

Brass Armstrong

2B1050 Horizontal


Installation Specifications

Recommended for

Based on

Pump

Model Numbers

Maximum GPM

Installation Type

Copper-Fin Wtr Htr, CW(N,L) 0986-2066

90 GPM

Single Water Heater piped to Single Storage Tank

ARM3024PAB

Based on

Based on

Minimum Pipe Diameter

Connecting piping

2-1/2"

Maximum 45 feet straight pipe with 6-Elbows, 2-Unions,2-Ball Valves and 1-Cold Water Inlet Tee

IMPORTANT: Read the Copper-fin 495-2065 Installation and Operation Manual. If the planned system exceeds
the pump capacity in flow and/or head see “Pump-REC-All Pumps” for alternate pumps and pump curves.



OIL PORT

A

C

16”

19-1/2”













B

D

11-1/2”





2