beautypg.com

Lochinvar PUMP-REC-05 REV B User Manual

Pump, Pump-rec-05 rev b, Recommendation

background image



PUMP-Rec-05 Rev B

PUMP

Recommendation

PUMP RECOMMENDATION FOR

COPPER-FIN 0495-0745 WATER HEATER

Pump Specifications

Part No.

HorsePower

Flanges

Valute Material

Flange Material

Vendor

Vendor Product Series

Orientation

ARM3044PAB 1/4

2" Bronze

Bronze

Armstrong

LS45

Horizontal


Installation Specifications

Recommended for

Based on

Pump

Model Numbers

Maximum GPM

Installation Type

Copper-Fin Wtr Htr, CW(N,L) 0495-0745

55 GPM

Single Water Heater piped to Single Storage Tank

ARM3044PAB

Based on

Based on

Minimum Pipe Diameter

Connecting piping

2"

Maximum 45 feet straight pipe with 6-Elbows, 2-Unions,2-Ball Valves and 1-Cold Water Inlet Tee

IMPORTANT: Read the Copper-fin 495-2065 Installation and Operation Manual. If the planned system exceeds
the pump capacity in flow and/or head see “Pump Curves-All Pumps” for alternate pumps and pump curves.


OIL PORT

A

C

12-1/2”

15-3/4”

0

10

20

30

40

50

60

70

5

10

15

20

80

90

100

110

LS-45

TO

TAL HEAD IN

FEET

CAPACITY IN U.S. GALLONS PER MINUTE













B

D

10”








1