Sloped Ceiling Installation:
The following information is from the National Fire
Protection Association and is listed in Fire Code 72. Install
Smoke Alarms on sloped, peaked or cathedral ceilings at, or
within 3 ft (0.9m) of the highest point (measured horizon-
tally). NFPA 72 states “Smoke alarms in rooms with ceiling
slopes greater than 1 ft to 8 ft (.3 m-2.4 m) horizontally
shall be located on the high side of the room”. NFPA 72
states “A row of alarms shall be spaced and located within
3 ft (0.9 m) of the peak of the ceiling measured horizontal-
ly” (See figure 2).
10
FIGURE 1
Operating and Installation Instructions
See also other documents in the category Kidde Safety:
- 3SF23/9HI (10 pages)
- 0976 (14 pages)
- 1235E (2 pages)
- 1285 (7 pages)
- 440376 (7 pages)
- KN-COB-DP-LS (2 pages)
- KN-COP-DP-LS (18 pages)
- 468093 (2 pages)
- SM120X (1 page)
- Smoke Alarm 914 (23 pages)
- 440379 (6 pages)
- 1275E (2 pages)
- KN-COP-DP-LS (2 pages)
- SL177i (2 pages)
- PE9CA (12 pages)
- 440375 (6 pages)
- 1276CA (14 pages)
- I9080 (10 pages)
- I9080 (18 pages)
- RF-SND (11 pages)
- Smoke Alarm (2 pages)
- KN-COPP-B-LS (2 pages)
- RF-SM-ACDC User Guide (22 pages)
- KN-COSM-B (18 pages)
- KN-COSM-BA (30 pages)
- i12060A (18 pages)
- i12060 (17 pages)
- PI 2000 (7 pages)
- SIRIUS TM0109 (4 pages)
- PI9000 (2 pages)
- 914 (2 pages)
- HD135F (2 pages)
- KN-COB-IC (12 pages)
- KN-COB-IC (23 pages)
- 0910 (2 pages)
- Strobe Light SL177 (26 pages)
- 1296 (2 pages)
- TM0098 (4 pages)
- 976 (2 pages)
- KN-COB-IC (25 pages)
- SMOKE AND CARBON MONOXIDE ALARM (106 pages)
- I9070 (17 pages)
- 0915 (6 pages)
- 9 Volt Battery Operated Photoelectric/Ionization Smoke Alarm PI9000 (26 pages)