4-4 Troubleshooting
Generator
Problem
Possible Cause
Corrective Action
No AC output
Circuit breaker in OFF position
Reset breaker to ON position
No AC output
Circuit breaker tripped due to overload on
generator set
Reduce load. See Wattage Requirements.
Reset breaker to ON position.
Ship-to-shore transfer switch in “OFF”or
“SHORE”position
Turn switch to generator power
No DC power to controller
Check battery connections
Controller fuse blown
Replace fuse
Generator malfunction such as capacitor
or other internal fault
See authorized Kohler service
dealer/distributor
Low output or
excessive drop in
Engine speed too low
Adjust governor
Low output or
excessive drop in
voltage
Generator overloaded
Reduce load. See Wattage Requirements.
voltage
Engine in poor condition
If routine services are performed and
condition persists, see authorized Kohler
dealer/distributor
Defective capacitor
See authorized Kohler service
dealer/distributor
High generator
output voltage
Defective capacitor and/or poor wiring
connections
See authorized Kohler service
dealer/distributor
output voltage
Excessive speed or frequency
Adjust governor. Check governor linkage
and spring for damage or binding.
Will not crank
No DC power to controller
Check battery connections
Will not crank
Controller circuit fuse blown
Replace fuse and attempt start-up. If fuse
blows again, contact authorized Kohler
service dealer/distributor.