beautypg.com

Generator – Kohler 3.5CFZ User Manual

Page 17

background image

TP-5695 12/93

1-2 Specifications

Generator

3.5CFZ

5CFZ

Rated kW

3.5

5

Frequency--Hz

50

50

Rated Voltage

110 Volt, 2&3 Wire, Single Phase or 110/220 Volt, 3 Wire, Single Phase

Rated Amps (110 Volt)

31.8

45.5

Rated Amps (220 Volt)

15.9

22.7

Rotor Resistance (cold) (ohms)

4--5

4--5

Stator Resistance (cold) (ohms)*
Leads:
1--2, 3--4

0.8

0.8

55--66

4.2

4.2

B1--B2

0.08

0.08

4CZ

6.5CZ

Rated kW

4

6.5

Frequency--Hz

60

60

Rated Voltage

120 Volt, 2&3 Wire, Single Phase or 120/240 Volt, 3 Wire, Single Phase

Rated Amps (120 Volt)

33.3

54.2

Rated Amps (240 Volt)

16.7

27.1

Rotor Resistance (cold) (ohms)

3--4

4--5

Stator Resistance (cold) (ohms)*
Leads:
1--2, 3--4

0.06

0.04

55--66

1.9

2.4

B1--B2

0.09

0.06

3.5CFZ/4CZ

5CFZ/6.5CZ

Generator Type

Two-Pole, Rotating Field

Voltage Regulation

±5%

Frequency Regulation

±5%

Angular Operation (Max.)

(in all directions)

20°Continuous

Excitation Method

Brushless, Exciter Winding/Capacitor

Coupling Type

Tapered Shaft--Thru-Bolt

Stator Bolt Torque in. lbs. (Nm)

260 (29)

Thru-Bolt Torque ft. lbs. (Nm)

37 (50)

Number of Output Leads

4, Reconnectable

Insulation (Rotor and Stator)

Class F, Epoxy Varnish, Vacuum Impregnated

Winding Material

Copper

Bearing, Number and Type

1, Replaceable Ball

Circuit Protection:
Controller

Replaceable 10-Amp Fuse

Battery Charging

Replaceable 10-Amp Fuse

AC Circuit Breakers

Optional

* Most ohmmeters will not give accurate readings when measuring less than 1 ohm. The stator can be

considered good if a low resistance reading (continuity) is obtained and there is no evidence of shorted

windings (discoloration). Do not confuse a low resistance reading with a reading indicating a shorted winding.