Architectural and Engineering

Specifications

The smoke alarm shall be Kidde Model i4618 or approved equal. It

shall be powered by a 120VAC, 60Hz source along with a 9V battery back-

up. The unit shall incorporate an ionization sensor with nominal sensitivity

of 0.50 to .92%/ft. The temperature operating range shall be between 40°F

and 100°F (4°C and 38°C) and the humidity operating range shall be up to

85% relative humidity.

The smoke alarm can be installed on any standard single gang electri-

cal box, up to a 4” octagon junction box. The electrical connection (to the

alarm) shall be made with a plug-in connector. A maximum of 24 Kidde

devices can be interconnected in a multiple station arrangement. The

interconnect system must not exceed the NFPA (National Fire Protection

Association) limit of 18 initiating devices, of which 12 can be smoke alarms.

With 18 initiating devices (Smoke, heat, CO, etc), interconnected, it is still

possible to interconnect 6 strobe lights and/or relay modules. The alarm

shall provide optional tamper resistance that deters removal of the unit

from the wall or ceiling. No additional pieces shall be required to activate

this feature.

The alarm shall include an easy access battery compartment that is

opened and closed by sliding the battery door. The 9V battery carrier will

ensure proper battery backup protection by not allowing the battery door

to close if the battery is placed in the unit incorrectly or if a battery is not

present.

The unit shall include a piezoelectric horn that is rated at 85 decibels

at 10 feet. The unit shall include the Smart Hush

TM

feature that silences the

unit for approximately 8 minutes if a nuisance condition occurs.

The unit shall incorporate red and green LED indicators. The green

LED (when illuminated) indicates the presence of AC power. The red LED

(located under the TEST/Hush button) has four modes of operation:

Standby Condition: The red LED will flash every 30-40 seconds to indi-

cate that the smoke alarm is operating properly. Alarm Condition: When

the alarm senses products of combustion and goes into alarm the red LED

will flash one flash per second. The flashing LED and pulsating alarm will

continue until the air is cleared. When units are interconnected, only the red

LED of the alarm that senses the smoke or is being tested (the originating

unit) will flash. All other units in the interconnected system will sound an

alarm but their red LED’s will NOT flash. Alarm Memory: This smoke alarm

is equipped with an alarm memory, which provides a visual indication when

an alarm has been activated. The red LED will illuminate for about 1.5

seconds every 16 seconds to indicate the memory condition. Smart Hush

TM

Mode: The red LED will illuminate for 1.5 seconds every 8 seconds,

indicating the smoke alarm is in the Smart Hush

TM

Mode.

The unit shall at a minimum meet the requirements of UL217, NFPA72,

and (chapter 11), The State of California Fire Marshall, NFPA101 (0ne and

two family dwellings), Federal Housing Authority (FHA), Housing and Urban

Development (HUD).

FUSE OR CIRCUIT BREAKER

BLACK

WHITE

RED

L

N

First

Alarm

Additional

Alarms

Ordering Information

Ordering

Dimensions

Number

UPC

I2F5

Pack Quantity

(w x d x h inches)

Weight Skid

21007581

0-47871-07581-2

100-47871-07581-9

Cut Case (6 units)

6.63 x 13.25 x 6.25

3 lbs

1008

21007584

0-47871-07584-3

100-47871-07584-0

Bulk Pack (36 units)

13.25 x 19.5 x 19.5

18 lbs

1296

21007585

0-47871-07585-0

100-47871-07585-7

Cut Case (4 units)

7.94 x 13.38 x 11.75

2 lbs

390

21007588

0-47871-07588-1

100-47871-07588-8

Bulk Pack (4 units)

6.5 x 9 x 6.5

2 lbs

720

21007583

0-47871-07583-6

100-47871-07583-3

Cut Case (6 units)

6.63 x 13.25 x 6.25

3 lbs

1008

Not for sale by individual unit

120V AC Wire-In Smoke Alarm
Slide Load Front Battery Door

Model i4618

Technical Specifications

Model:

i4618

UPC:

0-47871-07581-2

Power Source:

120VAC (

80mA Max)

Sensor:

Ionization

Audio Alarm:

85dB at 10ft

Temperature Range: 40˚F (4.4˚C) to 100˚F (37.8˚C)
Humidity Range:

Up to 85% relative humidity (RH)

Size:

5.6” in diameter x 1.8” depth

Weight:

.5lbs

Interconnects:

Up to 24 Kidde devices

LED:

Green, receiving ac power

Red, 4 modes of operation

Warranty:

5 year limited

Installation of Smoke Alarm

The smoke alarm should be installed to comply with all local codes having jurisdiction in your area,

Article 760 of the National Electric Code, and NFPA 72. Make certain all alarms are wired to a single,

continuous (non-switched) power line, which is not protected by a ground fault interrupter. A maxi-

mum of 1000 ft. of wire can be used in the interconnect system. Use standard UL listed household

wire as required by code.