beautypg.com

Nexos english 120 ac _layout 1, Installation instructions, Installation manual – Klaxon Nexus 120 AC User Manual

Page 2: Nexus 120 ac sounder & sounder-beacon, Installation important, Wiring, Technical specification, Controls

background image

Installation Manual

Installation
IMPORTANT

a. The unit should be fitted with a fused spur incorporating an all pole

disconnection device providing 3mm contact separation in all poles.
Ensure fuse, cable size and gland type are rated sufficiently for the
total load on the sounder circuit.

b. Isolate the unit from the electricity supply before removing the cover.

Only suitably qualified personnel should gain access to the unit to
perform adjustments to the tone or volume. WARNING: no user
serviceable parts contained within the unit.

c. The sounder is installed by first mounting the base unit and making the

external wring connections to the base. The head unit then automatically

connects when it is attached to the base.

d. The sounder head is separated from the base by unlocking the four

¼-turn fasteners in the corners of the sounder. (Recommended
screwdriver: Philips No. 2, min 100mm long).

e. Note that the head only fits onto the base one way around. If a beacon

is fitted, care should be taken when mounting the base to ensure that
the beacon will be positioned in the desired orientation after the
sounder is attached.

Wiring

a. Power: Note that the sounder and beacon have separate power

terminals, marked as follows:

b. Remote Tone Switching (If required): Externally link control terminals

as shown below.

EN

Sounder
Beacon (Where fitted)

Device

Common (Neutral)

110V

230V

Alarm Stage

Example Signal

Activation

Technical Specification:

Supply Voltage Range

110/230V 50/60Hz

Current

Sounder - 200mA max.

Beacon (where fitted) - 70mA

Peak Sound Level

111-120 dBA at 1m*

Number of Tones

64

Frequency Range

340 - 2900 Hz*

Volume Control

20 dBA typical

Remote Tone Switching

Provision for 3 volt-free contact

activated alarm stages

Operating Temperature

- 25°C to +55°C

Casing

High Impact Polycarbonate/ABS

IP Rating

IP66 with suitable cable glands

Synchronisation

Automatic with Klaxon Nexus and

Sonos Sounders

*depends on selected tone.

The European directive “Waste Electrical and Electronic Equipment” (WEEE)
aims to minimise the impact of electrical and electronic equipment waste on
the environment and human health. To conform with this directive, electrical
equipment marked with this symbol must not be disposed of in European public
disposal systems. European users of electrical equipment must now return
end-of-life equipment for disposal. Further information can be found on the
following website: http://www.recyclethis.info/.

S

2

+

-

S

1

2 3 0 V

~

110 V

~

N

2 3 0 V

~

110 V

~

S 3

S 2

0

S

2

+

-

S

1

2 3 0 V

~

110 V

~

N

2 3 0 V

~

110 V

~

S 3

S 2

0

2nd Stage
3rd Stage

Beacon L

Sounder L

Common N

1st Unit

2nd Unit

From controller

To the next unit

Nexus 120 AC Sounder & Sounder-Beacon

Installation Instructions

N

N

110V

~

110V

~

230V

~

230V

~

S2

S3

Stage 1

‘Alert’

No Connection (Default)

Stage 2

‘Evacuate’

Link Terminal

to terminal

Stage 3

‘All Clear’

Link Terminal

to terminal

Controls

a. Tone Selection

The first and second stage alarm tones are independently set using
6-way dipswitches S1 and S2 respectively. The required settings are
shown in the table overleaf. The third stage alarm tone is pre-set to
complement the selected first stage tone as shown in the table.

b. Volume Control

The sound output of the unit can be reduced by up to 20dBA by
adjusting the potentiometer.