Klaxon Nexus 110 AC User Manual
Installation instructions, Fr nl en de es pt it pl se dk, Nexus 110 ac sounder & sounder-beacon
Nexus 110 AC Sounder & Sounder-Beacon
Installation Instructions
Klaxon Signals Ltd, Oldham, OL4 1HW, UK
Phone +44 161 287 5555
Fax +44 161 287 5511
E-mail [email protected]
Issue 4 (June 2008) 18-186459
Copyright © Klaxon Signals Ltd
www.klaxonsignals.com
Tone
Tone Type
Tone Description / Application
Dip Switch
3rd Stage
Peak Sound
(S1/S2)
Tone
Level (dBA@1m)
1.
970Hz (BS5839-1:2002)
O-O-O-O-O-O
18
110
2.
800Hz/970Hz @ 2Hz (BS5839-1:2002)
O-O-O-O-O-I
1
110
3.
800Hz – 970Hz @ 1Hz (BS5839-1:2002)
O-O-O-O-I-O
1
110
4.
970Hz 1s OFF/1s ON (Apollo Fire Systems Alert Tone, BS5839-1:2002)
O-O-O-O-I-I
1
110
5.
970Hz, 0.5s/ 630Hz, 0.5s (Apollo Fire Systems Evacuate Tone, BS5839-1:2002)
O-O-O-I-O-O
1
110
6.
554Hz, 0.1s/ 440Hz, 0.4s (France – AFNOR NF S 32 001 )
O-O-O-I-O-I
1
107
7.
500 – 1200Hz, 3.5s/ 0.5s OFF (Netherlands – NEN 2575:2000)
O-O-O-I-I-O
1
110
8.
420Hz 0.625s ON/0.625s OFF (Australia AS1670 Alert tone)
O - O - O - I - I - I
1
105
9.
500 – 1200Hz, 0.5s/ 0.5s OFF x 3/1.5s OFF (Australia AS1670 Evacuation tone)
O-O-I-O-O-O
1
110
10.
550Hz/440Hz @ 0.5Hz
O-O-I-O-O-I
19
107
11.
970Hz, 0.5s ON/0.5s OFF x 3/ 1.5s OFF (ISO 8201 Low tone)
O-O-I-O-I-O
1
110
12.
2850Hz, 0.5s ON/0.5s OFF x 3/1.5s OFF (ISO 8201 High tone)
O - O - I - O - I - I
1
112
13.
1200Hz – 500Hz @ 1Hz (DIN 33 404)
O-O-I-I-O-O
1
110
14.
400Hz
O - O - I - I - O - I
18
105
15.
550Hz, 0.7s/1000Hz, 0.33s
O - O - I - I - I - O
1
111
16.
1500Hz – 2700Hz @ 3Hz (Vandal Alarm)
O - O - I - I - I - I
1
116
17.
Simulated Bell
O-I-O-O-O-O
1
112
18.
2130Hz
O-I-O-O-O-I
1
113
19.
660Hz
O-I-O-O-I-O
10
109
20.
660Hz 1.8s ON/1.8s OFF
O - I - O - O - I - I
19
108
21.
660Hz 0.15s ON/0.15s OFF
O-I-O-I-O-O
19
107
22.
510Hz, 0.25s/ 610Hz, 0.25s
O - I - O - I - O - I
1
107
23.
800/1000Hz 0.5s each (1Hz)
O - I - O - I - I - O
1
111
24.
250Hz – 1200Hz @ 12Hz
O - I - O - I - I - I
1
105
25.
500Hz – 1200Hz @ 0.33Hz.
O-I-I-O-O-O
1
110
26.
2400Hz – 2900Hz @ 9Hz
O - I - I - O - O - I
1
116
27.
2400Hz – 2900Hz @ 3Hz
O - I - I - O - I - O
1
116
28.
800Hz – 970Hz @ 100Hz
O - I - I - O - I - I
1
110
29.
800Hz – 970Hz @ 9Hz
O - I - I - I - O - O
1
110
30.
800Hz – 970Hz @ 3Hz
O - I - I - I - O - I
1
110
31.
800Hz, 0.25s ON/1s OFF
O - I - I - I - I - O
1
108
32.
500Hz – 1200Hz, 3.75s/0.25s OFF (AS2220)
O - I - I - I - I - I
1
110
33.
340Hz
I-O-O-O-O-O
1
106
34.
1000Hz
I-O-O-O-O-I
18
111
35.
1400Hz – 1600Hz, 1s/1600Hz – 1400Hz, 0.5s (NF 48-265)
I-O-O-O-I-O
1
110
36.
660Hz 6.5s ON/13s OFF
I - O - O - O - I - I
19
108
37.
1000Hz/2000Hz, 1s each
I-O-O-I-O-O
1
113
38.
720Hz, 0.7s ON/0.3s OFF
I - O - O - I - O - I
1
106
39.
970Hz, 0.25s ON/OFF
I - O - O - I - I - O
1
110
40.
2800Hz, 1s ON/OFF
I - O - O - I - I - I
1
113
41.
2800Hz 0.25s ON/OFF
I-O-I-O-O-O
1
113
42.
2400/2900 @ 2Hz
I - O - I - O - O - I
1
115
43.
Chime, 554Hz/440Hz Single shot ‘ding dong’
I - O - I - O - I - O
1
104
44.
Chime, 554Hz/440Hz Repeating ‘ding dong’
I - O - I - O - I - I
1
107
45.
Chime, 970Hz/800Hz Single shot ‘ding dong’
I- O - I - I - O - O
1
106
46.
Chime, 970Hz/800Hz Repeating ‘ding dong’
I - O - I - I - O - I
1
106
47.
Hooter, Repeating
I - O - I - I - I - O
1
107
48.
Gentle alarm - Tone 2, rises slowly to full volume over 30s
I - O - I - I - I - I
1
109
49.
Time-Out Alarm – As Tone 2, cuts off after 10 mins
I-I-O-O-O-O
1
109
50.
Time-Out Alarm – As Tone 2, cuts off after 2 mins
I - I - O - O - O - I
1
109
51.
750Hz 0.33s ON/0.51s OFF
I - I - O - O - I - O
1
106
52.
750Hz 0.51s ON/0.33s OFF
I - I - O - O - I - I
1
107
53.
550Hz, 0.33s/1000Hz, 0.7s
I - I - O - I - O - O
1
111
54.
600Hz – 900Hz/ 0.9s
I - I - O - I - O - I
1
109
55.
660Hz – 680Hz/ 0.9s
I - I - O - I - I - O
1
105
56.
670Hz – 725Hz/ 0.9s
I - I - O - I - I - I
1
107
57.
920Hz – 750Hz/ 0.9s
I - I - I - O - O - O
1
110
58.
700Hz - 900Hz, 0.3s/0.6s OFF
I - I - I - O - O - I
1
109
59.
900Hz - 760Hz, 0.6s/0.3s OFF
I - I - I - O - I - O
1
110
60.
750Hz
I - I - I - O - I - I
18
107
61.
Power Only – Use with Stage 3 control for manual/intermittent chime triggering
I - I - I - I - O - O
43
62.
Power Only – Use with Stage 3 control for manual/intermittent chime triggering
I - I - I - I - O - I
43
63.
Power Only – Use with Stage 3 control for manual/intermittent horn triggering
I - I - I - I - I - O
47
64.
Reserved for future use
I - I - I - I - I - I
FR
NL
EN
DE
ES
PT
IT
PL
SE