Architectural and Engineering
Specifications

The smoke alarm shall be Kidde Unit 1296E or approved equal. It shall be
powered by a 120VAC, 60Hz source along with a 9V battery backup. The unit
shall incorporate an ionization sensor with nominal sensitivity of 0.84%/ft. The
temperature operation range shall be between 40˚F and 100˚F (4˚C and 38˚C)
and the humidity operation range shall be 5% - 95% relative humidity.

The smoke alarm can be installed on any standard single gang electrical

box, up to a 4” octagon junction box. The electrical connection (to the alarm)
shall be made with a plug-in connector. A maximum of 24 Kidde devices can
be interconnected in a multiple station arrangement. The interconnect system
must not exceed the NFPA (National Fire Protection Association) limit of 18
initiating devices (Smoke, heat, CO, etc) interconnected, it is still possible to
interconnect 6 strobe lights and or relay modules. The alarm shall provide
optional tamper resistance that deters removal of the unit from the wall or
ceiling.

The unit shall include a piezoelectric horn that is rated at 85dB at 10ft.

The unit shall incorporate 2 LED’s. A green LED will be constantly “ON”
when AC power is present. A red LED will flash once approximately every
30-40 seconds to indicate that the smoke alarm is operating properly and will
flash rapidly when the unit is alarming and will remain so until the air is
cleared. The red LED will be on while test B button is being pressed and will
illuminate for about 1.5 seconds every 16 seconds to indicate the memory
condition until unit is reset.

The unit shall incorporate two test buttons. Test button A shall test all

the electronic circuitry, horn, and battery. Test button B shall test the alarms
senor sensitivity.

The unit shall at a minimum meet the requirements of UL217, NFPA72,

(chapter 10 & 11 2002 edition) The State of California Fire Marshall, NFPA101
(One and two family dwellings, Federal Housing Authority (FHA), Housing and
Urban Development (HUD).

UTHA / UTGT Compliant
Smoke Alarm

Model 1296

Technical Specifications

Model Number:

1296

UPC:

0-47871-05127-4

Power Source:

120VAC, 60HZ, 9V battery backup

Sensor:

Ionization

Audio Alarm:

85dB at 10ft

Temperature Range: 40˚F (4.4˚C) to 100˚F (37.8˚C)

Humidity Range:

5%-95% relative humidity (RH)

Size:

5.6” in diameter x 1.55” depth

Weight:

.5lb

Interconnects:

Up to 24 Kidde devices

LED:

Green, AC power present
Red, alarm mode

Warranty:

5 year limited

Installation of Smoke Alarm

The smoke alarm should be installed to comply with all local codes having jurisdic-
tion in your area, Article 760 of the National Electric Code, and NFPA 72. Make
certain all alarms are wired to a single, continuous (non-switched) power line,
which is not protected by a ground fault interrupter. A maximum of 1000 ft. of
wire can be used in the interconnect system.

FUSE OR CIRCUIT BREAKER

BLACK

WHITE

RED

L

N

First
Alarm

Additional
Alarms

Ordering Information

Gift Box UPC: 0-47871-05127-4

**Not for sale by individual unit

MASTER PACK

6

1

UNIT

Part

Dimensions

Case/

Layers/

Skid

Number

I 2 of 5

Pack Quantity

(w x d x h inches)

Weight

Skid

Skid

Weight

21005186**

N/A

Individual

5.75 x 1.75 x 5.75

.5lb

N/A

N/A

N/A

21005127

100 47871 05127 1

Master (6 units)

6 x 11.5 x 6

3.5lbs

162

6

567lbs

5.6"

1.55"