beautypg.com

Analog output-pneumatic (ao-p) module, Product overview, Siemens building technologies, inc. 9 – Siemens 125-5033 User Manual

Page 17: Figure 8. pneumatic actuator, Figure 9. ao-p module

background image

Product Overview

Siemens Building Technologies, Inc.

9

Figure 8. Pneumatic Actuator.

Analog Output-Pneumatic (AO-P) Module

The Analog Output-Pneumatic (AO-P) Module is an electric-to-pneumatic interface between
the Fume Hood Controller and the pneumatic actuator. The AO-P Module translates electrical
signals from the Fume Hood Controller into pneumatic signals that command the actuator.
The AO-P Module consists of two industrial grade solenoids that supply or bleed air to the
actuator by using a pulse modulation technique. See Figure 9. Minimum air supply to the AO-
P Module is 18 psi and the maximum is 30 psi. The valves are rated for 24 Vac.

5.00" (127.0mm)

3.70"

(94.0mm)

SUPPL

Y

COMMON

EXHA

UST

SUPPLY

S

(SUPPL

Y)

18-30 PSI

R

(A
CTU

A

T

OR)

EXHAUST

FUM0240R1

Figure 9. AO-P Module.