beautypg.com

4 cabling, Cabling – Studer Innotec XTH 3000-12 User Manual

Page 9

background image

Steca

Xtender

Installation and Operating Instructions 723.932 Xtender V0.511

Seite 9

Pos.

Denominati
on

Description

Comment

1 ON/OFF

Main switch

Main on/off switch

See chapter Automatic load shedding of
the inverter (2 sequences)
7.1 – p 26.

2

Temp. Sens Connector for the battery

temperature sensor

See chapter 6.2.11 – p. 23.
Only connect the original Steca BTS-01
sensor

3

Com. Bus

Double connector for
connecting peripherals such as
the RCC002/03 or other
Xtender units

4

O / T
(Open /
Terminated)

Switch for terminating the
communication bus.

See chapter 4.5.8 – p. 16.
The two termination switches (4) for the
communication bus both remain in
position T (terminated) except when both
connectors are in use.

5

--

3.3 V (CR-2032) lithium ion
type battery socket

Used as a permanent supply for the
internal clock. See chapter 6.2.10 – p 23.

6

--

Jumper for programming the
off/on switch by dry contact

See chapter 6.2.11 – p. 23 and fig. 8b
point (6) and (7). They are positioned at
A-1/2 and B-2/3 by default

7 REMOTE

ON/OFF

Connection terminals for dry
on/off remote connection.

See chapter 6.2.11 – p. 23).
When the control via dry contact is not
being used, a bridge must be present
between the two terminals.

8 AUXILIARY

CONTACT

Auxiliary contact

See chapter 6.2.9 – p. 23
Take care not to exceed the admissible
loads

9

--

Activation indicators for
auxiliary contacts 1 and 2

See chapter 6.2.9 – p. 23

10

L1/L2/L3

Phase selection jumpers.

See chapter 6.3.1. – p. 24.
Jumper default at position L1

11

+BAT

Positive pole battery
connection terminals

12

-BAT

Negative pole battery
connection terminals

Carefully read chapter 4.5 – p. 12
Take care with the polarity of the battery
and when tightening the clamp.

13

AC Input

Connection terminals for the
alternative power supply
(generator or public network)

See chapter 0 - p. 16.
Note: It is imperative that the PE terminal
be connected.

14

AC Output

Connection terminals for the
device output.

See chapter 4.5.5 - p. 16.
Note: Increased voltages may appear on
the terminals, even in the absence of
voltage at the input of the inverter.

4 Cabling

The connection of the Xtender inverter / charger is an important installation step.
It may only be carried out by qualified personnel and in accordance with the applicable local
regulations and standards. The installation must always comply with these standards.
Pay attention that connections are completely tightened and that each wire is connected at the
right place.