14 Table of standard configurations

No. of

config.

Denomination / description

Fact.

value

Mod.

value

G1

1

kVA

G2

2

kVA

G3

3

kVA

1107 Maximum current of the AC source

A

30

3.5

7

12

1108 Undervoltage of the empty battery

V/cell

1.9

1109 Sub-voltage of the charged battery

V/cell

1.75

1110 Restart voltage of the inverter after undervoltage of the

battery

V/cell

2

1111 Automatic startup at energisation

No

1111 Automatic startup at energisation of the battery

No

1112 Inverter

frequency

Hz

50

1121 Maximum DC voltage for stopping the Xtender

V/cell

2.84

1126 Source backup (smart boost) permitted

No

1133 Number of restarts after stoppage

2

1138 Battery charge current

A

80

1139 Battery voltage correction according to the temperature

mV/°
C/cell

-5

1140 Battery maintenance voltage

V/cell

2.27

1156 Battery absorption voltage

V/cell

2.4

1157 Duration of absorption

h

2

1159 Current at end of absorption

Adc

2

1187 Sensitivity of the charge detection

3

1190 Duration of undervoltage of battery before disconnection

min.

3

1191 Dynamic compensation for undervoltage

Yes

1198 Time elapsing before transfer relay opens

sec.

0

5

1199 ACin voltage causing the opening of the transfer relay

Vac

180

1200 Immediate open critical threshold for the transfer

Vac

50

1300 Number of overloads permitted before definite stoppage

-- 2

1303 Number of battery overvoltages accepted before definite

stoppage

-- 3

1304 Number of battery undervoltages permitted before definite

stoppage

-- 3

1309 Minimum ACin voltage to authorise charging

Vac

185

1403 Period for counting battery overvoltages

sec.

30

1404 Period for counting battery undervoltages

sec.

30

1432 Maximum ACin voltage to switch to inverter mode

Vac

265

1436 Authorise exceeding of the input current limit without

interrupting the transfer

No

1470 ACin voltage hysteresis for closing the transfer relay

Vac

20

1485 Automatic earth-neutral connection in inverter mode

No

1488 Serious undervoltage of the battery

V/cell

1.5

1505 Delta of higher frequency accepted

Hz

15

1506 Delta of lower frequency accepted

Hz

5

1286 Output

voltage

Vac

227