Plan, Marley, Sigma steel cooling tower – SPX Cooling Technologies Marley Sigma Steel User Manual

Page 7: Engineering data : support

background image

Marley

/

Sigma Steel

Cooling Tower

/

Engineering Data : Support

7

Plan

A

SPACES AT 4'-0" =

L

6"

W

OVERALL OF B

ASIN

SUMP

OVERFLOW

AIR INLET FACE

AIR INLET FACE

CASED ENDW

ALL F

ACE

CASED ENDW

ALL F

ACE

PRIMARY SUPPORT

BEAM

INTERMEDIATE

BEAM

NOTE

1 Use this bulletin for preliminary layouts only. Obtain cur-

rent drawings from your Marley sales representative.

2 Steel beams must include

7

8

" dia. holes to accept anchor bolts

provided with tower. Other contractors or purchaser must

design and erect supporting steel.

3 Maintain at least 2'-0" of clear space at tower endwalls for

construction purposes. Air inlet faces must have unobstructed

air supply. If obstructions exist nearby, consult your Marley

sales representative.

4 Operating weight is wet weight of tower and steel basin,

including 6" of water in the cold water basin.

5 View shown is typical single cell beam arrangement.

1'-6"

6"

RECOMMENDED

OPERATING WATER LEVEL

Section

Tower

Model

Dimensions

Operating Weight lb

A

W

L

Single Fan Cell

Each Cell Add

121-111

3

23'-8"

12'-0"

37670

33150

122-111

4

25'-8"

16'-0"

49875

45105

123-111

4

27'-8"

16'-0"

50320

45230

124-111

5

27'-8"

20'-0"

60290

55200

125-111

5

31'-8"

20'-0"

67150

61220

126-111

6

31'-8"

24'-0"

77960

72115

127-111

7

31'-8"

28'-0"

88850

83590