Specifications

Specification Value

Marley

/

Sigma Steel

Cooling Tower

/

Specifications: Options

24

Convenience and Safety Options

Stairway:

9.3 Replace paragraph 9.3 with the fol-

lowing: A 30" wide, 45° steel stairway

with 8" rise and run, shall be provided

at the tower endwall rising from grade

(roof) to the fan deck elevation. Stair

treads shall be bar grating with checker

plate nosing, and shall be through

bolted to structural channel string-

ers. Stairway posts, guardrails and

toeboards shall be as specified per

Paragraph 9.2. Structural steel sup-

port columns for the stairway shall be

provided by the cooling tower manu-

facturer. Stairway foundation shall be

by others, designed in accordance with

drawings provided by the cooling tower

manufacturer. The entire stairway shall

be hot-dip galvanized after fabrication

and shall conform to OSHA standards.

Plenum Walkway:

9.1

Add the following to the end of this

paragraph: Provide a 30" wide bar grat-

ing walkway extending from one endwall

access door to the other in each cell. This

walkway shall be supported by a galva-

nized steel framework, and the top of the

grating shall be above the cold water basin

overflow level. If the cold water basin is

deeper than 4'-0", the walkway shall be

equipped with guardrails.

Ladder Extension:

9.4

Add the following paragraph in the

Access and Safety section: Provide

a ladder extension for connection to

the base of the ladder attached to

the tower casing. This extension shall

be long enough to rise from the roof

(grade) level to the base of the tower.

Anchorage and lateral bracing of the

ladder extension shall be by others.

Ladder Safety Cage:

9.3 Add the following to the end of this

paragraph: A heavy gauge galvanized

steel safety cage shall surround the

ladder, extending from a point approxi-

mately 7'-0" above the base of the

ladder to the top of the guardrail sur-

rounding the fan deck.

Although they are not necessary for routine operation and mainte-

nance, stairways do provide a safe and comfortable means of access to

the top of the tower that is often overlooked in the initial cooling tower

purchase. They are designed in straight-run or double-back configura-

tions to accommodate your site requirements.

This option permits freedom of movement for inspection or mainte-

nance within the tower without the need for wading boots or tower

drainage. It also helps prevent maintenance personnel from damag-

ing submerged accessories in the cold water basin (such as screens,

probes, basin heaters, etc.).

Many towers are installed such that the base of the tower is 2'-0" or

more above the roof or grade level. This makes it difficult to get up to

the base of the attached ladder. The ladder extension alleviates this

problem. Marley ladder extensions are available in standard 5'-0" and

11'-0" lengths, and will be field-cut to fit.

To meet OSHA guidelines, towers whose fan

decks are 20'-0" or more above roof or grade, and

which are equipped with ladders, are required to

have safety cages surrounding the ladders.