Specifications

Specification Value

Marley

/

Sigma Steel

Cooling Tower

/

Specifications: Options

21

Basin Heaters:

10.2 Add the following paragraph in the

Cold Water Basin section: Provide a

system of electric immersion heaters

and controls for each cell of the tower

to prevent freezing of water in the

collection basin during periods of shut-

down. The system shall consist of one

or more stainless steel electric immer-

sion heaters installed in the basin. A

NEMA 4 enclosure shall house a mag-

netic contactor to energize heaters; a

transformer to provide 24 volt control

circuit power; and a solid state circuit

board for temperature and low water

cutoff. A control probe shall be located

in the basin to monitor water level

and temperature. The system shall be

capable of maintaining 40°F water tem-

perature at an ambient air temperature

of __ °F.

Fan Motor Variable Speed Drive:

Marley All Weather ACH550 System

6.4 Add the following paragraph in the

Mechanical Equipment section when

VFD is used with customers Building

Management System: A complete

UL listed Variable Speed Drive system

in a NEMA 1 indoor, NEMA 12 indoor

or NEMA 3R outdoor enclosure shall

be provided. The VFD shall use PWM

technology with IGBT switching and

integrated bypass design. VFD out put

switching shall not cause mechanical

issues with gearbox teeth or drive shafts.

The VFD shall catch a fan spinning in

the reverse direction without tripping.

The panel shall include a main discon-

nect with short circuit protection and

external operating handle, lockable in the

off position for safety. The VFD system

shall receive a speed reference signal

from the Building Management System

monitoring the tower fluid temperature.

As an option to receiving the speed

reference signal from a building manage-

ment system, the drive must have the

capability to receive a 4-20 ma tempera-

ture signal from an RTD transmitter. The

VFD shall have an internal PI regulator

to modulate fan speed maintaining set

point temperature. The drive's panel dis-

play shall be able to display the set-point

The basin heater components described at left represent our recom-

mendation for a reliable automatic system for the prevention of basin

freezing. They are shipped separately for installation at the job site.

The ambient air temperature that you fill in should be the lowest 1%

level of winter temperature prevalent at site.

Marley VFD drive systems are designed to combine absolute tempera-

ture control with ideal energy management. The cooling tower user

selects a cold water temperature and the drive system will vary the

fan speed to maintain that temperature. Precise temperature control is

accomplished with far less stress to the mechanical equipment com-

ponents. The improved energy management provides fast payback.

Indeed, many utilities offer generous rebates for users having installed

VFD drives.