Ammonia and halocarbon gas monitors, Specifications – Sierra Monitor Corporation 2050 User Manual
Page 2

Model 2050/2060
Ammonia and Halocarbon Gas Monitors
SPECIFICATIONS
Indicators:
Green LED for Monitor “ON”/Safe
Red LED for Alarm
Sensor Type:
Solid-state metal oxide semiconductor
Alarm Setpoint::
2050 Series
100 ppm NH
3
2060 Series
R11
500 ppm
R12
500 ppm
R22
50 ppm
R113
100 ppm
R123
70 ppm
R134a
50 ppm
R141b
40 ppm
R142b
40 ppm
R500
40 ppm
R502
70 ppm
User adjustable with calibration over
range of 50 to 500 ppm
Calibration Gas:
2050 Series
80 ppm Hydrogen (H
2
)
2060 Series
150 ppm Carbon Monoxide (CO)
Power:
9-24 VDC, 250 mA
Signal Output::
2050-00/2060-00
Nominal 5 volt DC, source 25 mA. SAFE
and ALARM Signals
0.5 AMP dry contact, 100 VDC, 130 VAC
and audible
Response Time:
Less than 90 seconds
Operating Temperature Range:
-4
o
to 158
o
F (-20
o
to 70
o
C)
Enclosure Material:
Polystyrene
Size:
5.6 x 3.1 x 2.1 in. (14.2 x 7.9 x 5.3
cm)
Weight:
0.3 lb (0.15 Kg)
Sierra Monitor Corporation 1991 Tarob Court Milpitas, CA 95035 (408) 262-6611 (800) 727-4377 FAX: (408) 262-9042
Visit our website: www.sierramonitor.com E-mail: [email protected]
Outline and Dimensions
of Model 2050/2060
ORDERING INFORMATION
2050-00
Ammonia Gas Monitor
2060-00
Refrigerant/Halocarbon Gas Monitor
1200-26
Gas Sensor Calibrator w/2 gas cylinders
of calibration gas
1290-10
Gas Cylinder - Carbon Monoxide, 150 ppm
1290-11
Gas Cylinder - Hydrogen, 80 ppm
OTHER PRODUCTS
2102-00
Dual Channel Alarm Panel
© 2010 Sierra Monitor Corp. Rev. A-7/10