beautypg.com

Electrical • priming • winterize 8, Preparing to start the pump, Priming – Simer Pumps 2806E User Manual

Page 8: Winterizing the pump, Wiring chart – recommended wire and fuse sizes

background image

Electrical • Priming • Winterize

8

For parts or assistance, call Simer Customer Service at 1-800-468-7867

For parts or assistance, call Simer Customer Service at 1-800-468-7867

Priming

Explosion hazard . Never run pump against closed discharge.

To do so can boil water inside pump, causing hazardous pressure in unit,
risk of explosion and possibly scalding persons handling pump.

Burn Hazard . Never run pump dry. Running pump without

water may cause pump to overheat, damaging seal and possibly causing
burns to persons handling pump. Fill pump with water before starting.
1. Remove the priming plug from the pump and fill the pump, fill all

piping between the pump and the well, and make sure that all piping in
the well is full (Figure 6). If you have also installed a priming tee in the
suction piping, remove the plug from the tee and fill the suction piping.

2. Replace all fill plugs.
3. Power on! Start the pump. If you don’t have water after 2 or 3 minutes,

stop the pump and remove the fill plugs. Refill the pump and piping.
You may have to repeat this several times in order to get all the trapped
air out of the piping. A pump lifting water 25’ may take as long as
15 minutes to prime.

4. After the pump has built up pressure in the system and shut off, check

the pressure switch operation by opening a faucet or two and running
enough water out to bleed off pressure until the pump starts. The pump
should start when pressure drops to 30 PSI and stop when pressure
reaches 50 PSI. Run the pump through one or two complete cycles to
verify correct operation. This will also help clean the system of dirt and
scale dislodged during installation.

Winterizing the Pump

To prepare the pump for freezing temperatures:
1. Shut off power to the pump.
2. Relieve system pressure. Open a faucet and let it drain until water stops

flowing.

3. Drain the pump. Your pump may have a separate drain plug. Remove

this plug and let it drain.

Your pump may only have a plug or connection on the side of the
pump. Remove this and let the pump drain. Some water will remain in
the pump. A small amount of water left in the pump will not harm it if
it freezes.

Wiring Chart – Recommended Wire and Fuse Sizes

Motor HP

Volts

Max . Load

Amp

Branch Fuse

Rating Amp

Distance In Feet From Motor To Supply

0 - 100

101 - 200

201 - 300

301 - 400

401 - 500

AWG Wire Size (mm

2

)

1/2

115/230

9.9/4.95

15/15

14/14 (2/2)

14/14 (2/2)

12/14 (3.3/2)

10/14 (5.5/2)

10/12 (5.5/3.3)

Preparing to Start the Pump

Fill pump

and piping

through

priming tee.

Can fill downpipe

separately through

2nd priming tee.

Figure 6: Prime the Pump