IGWiPS200-1

Combination Input/Output Module
Channels ...............................................................1 analog input

1

analog

output

2

digital

inputs

2

digital

outputs

Channel Isolation..................................................All (except for the analog input channel)
Reverse Polarity Protection ..................................Yes
Analog Channel
Range.............................................................4-20

mA

Input

Impedance ............................................<170

Ohms

Repeatability..................................................0.2% of full scale
Resolution......................................................16-bit
Compatibility.................................................2-wire,

3-wire, 4-wire devices

Over-Voltage Rating .....................................42 Vdc maximum

Digital Input Channel
Input

Impedance ............................................20k

Ohms

Over-Voltage Rating ....................................100 Vac/Vdc maximum

Voltage ..........................................................5 to 36 Vac/Vdc

Digital Output Channel
Contact

Rating...............................................250 Vac / 30 Vdc, 2A

Type...............................................................Dry

contact, normally open

Power Input ..........................................................12 to 30 Vdc
Current Consumption ...........................................120 mA maximum
Operating Temperature Range..............................-40°C to 70°C (-40°F to 158°F)
Faceplate Label Colors .........................................Analog In section – Green

Analog Out section – Yellow

Digital In section – Blue

Digital Out section - Pink


Pulse Input Module
Channels ...............................................................2
Input Voltage ........................................................3.6 Vdc minimum (Single Edge Mode), 100 mVac P-P

(Differential Mode)

Input Frequency....................................................0-32 kHz
Pulse Width ..........................................................10 μSec minimum
Input Impedance ...................................................1k Ohms (low), 90k Ohms (high), Selectable
Coupling ...............................................................AC or DC, Selectable
Channel Isolation..................................................Optical
Reverse Polarity....................................................Yes, protected
Power Input ..........................................................12-30 Vdc
Backup Power Supply ..........................................12-30 Vdc
Current Consumption ...........................................50 mA maximum
Operating Temperature Range..............................-40°C to 70°C (-40°F to 158°F)
Faceplate Label Color...........................................Orange

Pulse Output Module
Channels ...............................................................2
Output...................................................................30 Vdc @ 250 mA maximum
External Voltage...................................................30 Vdc maximum
Frequency .............................................................0-32 kHz
Duty Cycle............................................................50%
Internal Pull-Up ....................................................1k Ohms
Channel Isolation..................................................No
Power Input ..........................................................12-30 Vdc
Power Consumption .............................................120 mA maximum
Operating Temperature Range..............................-40°C to 70°C (-40°F to 158°F)
Faceplate Label Color...........................................Orange

May 2007