UK Conditions: Cooling Indoor 23˚C DB 50% RH Outdoor 30˚C Heating Indoor 20˚C Outdoor 0˚C

Rating Conditions: Cooling Indoor 27˚C DB 19˚C WB Outdoor 35˚C DB 24˚C WB Heating Indoor 20˚C DB Outdoor 7˚C DB 6˚C WB

6

UK Conditions: Cooling Indoor 23˚C DB 50% RH Outdoor 30˚C Heating Indoor 20˚C Outdoor 0˚C

Rating Conditions: Cooling Indoor 27˚C DB 19˚C WB Outdoor 35˚C DB 24˚C WB Heating Indoor 20˚C DB Outdoor 7˚C DB 6˚C WB

ECOi Mini 4-6HP 2 Way Inverter Heat Pump VRF Systems

Wide operating range

The operating range for heating operation is to -20°C, the
cooling range is to -10°C. The remote controller temperature
setting offers a range from 16°C to 30°C.

SANYO’s policy of product development continues

with the expansion of the ECOi Mini, the 2 pipe

heat pump small VRF system specifically designed

for the European market.

Offering between 11kW and 16kW cooling capacity in 3 sizes
and up to 9 indoor units connected, the ECOi Mini sets new
standards of performance and flexibility.

Utilising R410A and DC inverter technology, SANYO offers
VRF to a new and growing market.

Forming a new key part of the SANYO VRF line up, the ECOi
Mini is compatible with the same indoor units and controls
of the electric and gas powered VRF range.

Features at a glance

• Single phase or three phase power supply

• One AMP start current

• DC inverter technology combined with R410A for excellent

efficiency

• COP of up to 4.34

• Diversity ratio 50-130%

• 150m pipe runs

• Cooling operation to -10°C

• Full range of indoor units and control options

• Compact outdoor unit 1230x940x340mm

Highest COPs - lowest running costs

HP

4

5

6

EER Cooling

4.06

3.66

3.39

COP Heating

4.34

4.10

3.84

Higher COPs - lower running costs

HP

8

10

12

14

16

18

20

22

24

26

28

30

32

34

36

38

40

42

44

46

48

EER Cooling

3.74

3.54

3.50

3.45

3.38

3.63

3.54

3.51

3.49

3.44

3.43

3.41

3.38

3.50

3.47

3.47

3.45

3.42

3.43

3.40

3.38

COP Heating

4.10

4.10

3.91

3.91

3.79

4.06

4.06

3.97

3.96

3.88

3.84

3.85

3.79

4.00

3.94

3.89

3.91

3.86

3.83

3.83

3.79

ECOi 2 Way - features at a glance

Actual length: 150m*

2

(Equivalent length: 175m)

System difference of

elevation: 50m *

1

Difference in elevation

between indoor units: 15m

*1: 40m if the outdoor unit is below the indoor unit.

*2: Total length of pipe: no more than 300m

ECOi 2 Way is a high-performance heat

pump system with excellent energy-saving

features, designed for creating a comfortable

environment when either heating or cooling

is required.

• Heat pump systems offer heating or cooling

• Single footprint size for all unit capacities

• DC inverter technology combined with R410A for excellent

efficiency

• System configuration from 8HP to 48HP

• Diversity ratio 50-130%

• Industry low outdoor unit sound levels: from 54.5dB(A)

• Quiet mode offers a further 3dB(A) reduction

• Extended pipe runs of up to 150m

• COPs up to 4.10

• Heating capacity to -20°C

• Connectability of 40 indoor units from 24HP upwards

• Units available from 8-16HP as single units

Extended compressor life

The compressor running time is monitored and optimised
by a microcomputer to ensure that there is no imbalance
in the operation times of compressors on the same
refrigerant circuit.

Save on piping cost

R410A with low pressure loss enables smaller pipe sizes.
This means reduced piping space, improved workability at
the site and reduced piping material costs.

Extended operating range - better output at lower

temperatures

The operating range for heating has been extended to
-15°C. The remote controller temperature setting for heating
operation has also been extended from 16°C to 30°C.

Longer piping means greater installation area

Reducing the refrigerant volume by reducing piping size has
extended the piping actual length to 150m (175m equivalent
piping length).

HP

4

5

6

Model name

SPW-CR365GXH56B/SPW-CR365GXH8B SPW-CR485GXH56B/SPW-CR485GXH8B SPW-CR605GXH56B/SPW-CR605GXH8B

Power supply

230V, 1 phase, 50/60Hz/400, 3 phase, 50/60Hz

Cooling capacity

kW

11.20

14.00

15.50

Heating capacity

kW

12.50

16.00

17.60

EER Cooling

4.06

3.66

3.39

COP Heating

4.34

4.10

3.84

Electric rating

Cooling

Running

amperes A

14.1/4.34

19.6/6.02

23.4/7.18

Power input kW

2.76

3.83

4.57

Heating

Running

amperes A

14.7/4.52

19.9/6.13

23.4/7.19

Power input kW

2.88

3.90

4.58

Recommended fuse size (motor

rated)

1ph 3ph

25/16

32/16

Dimensions (H/W/D)

mm

1,230x940x340

Net weight

kg

104

Air circulation

m

3

/min

100

Refrigerant amount at shipment

kg

3.5

Piping connection

Gas Inches

(mm)

5/8 (15.88)

3/4 (19.05)

Liquid Inches

(mm)

3/8 (9.52)

Operating sound normal mode

dB(A)

51.0

52.0

Operating sound quiet mode

48.0

49.0

Ambient temperature operating

range

Cooling

-10°C DB +43°C DB

Heating

-20°C DB +15°C DB

Maximum number of indoor units

6

8

9

* Condenser actual pipe connections may vary from above pipe connections shown, please refer to technical manuals for full details.

* Please refer to tube sizing charts for pipe selections and pipe length parameters.