beautypg.com

Installation, Figure 14 combo heating - air handler, Figure 15 combo heating - baseboard – John Wood Oil-Fired User Manual

Page 21: Figure 16 combo heating - in-floor loop

background image

Installation

The heating mode may be one of the following options:
1. A fan coil/air handler (Figure 14).
2. A hydronic baseboard (finned tube) loop (Figure 15).
3. A hydronic in-floor heating loop (Figure 16).
The following is a list of requirements for the installation of
the heating loop to the water heater.
1. Install shut-off valves and unions so that the water

heater can be isolated from the heating module should
servicing of the water heater become necessary.

2. Install a drain valve at the lowest point of the heating

loop so that water can be drained from the heating mod-
ule without affecting the water heater.

3. If the air handler does not have a venting means at the

highest point of the piping arrangement, install an air
bleed at the highest point of the plumbing arrangement.

4. If solenoid valves are used for zone heating applica-

tions, they must include electrical proof of valve full
open position and must be connected to the water
pump.

– 21 –

WATER

HEATER

200mm TO

300mm (8 in.

TO 12 in.)

HOT

OUTLET

EXPANSION TANK
(OPTIONAL)

MIXING
VALVE

COLD
INLET

CHECK VALVE (IF
USED REQUIRES
EXPANSION TANK)

COLD SUPPLY

HOSE BIB
(OPTIONAL)

FLOW
CONTROL

SUPPLY

RETURN

CHECK
VALVE

EXTERNAL
CIRCULATOR

AIR HANDLER

HOT WATER
TO HOUSE
FIXTURE

Figure 14 Combo Heating - Air Handler

C
H

M

INTERNAL
CIRCULATOR

DRAIN/PURGE
VALVE

WATER
HEATER

200mm TO

300mm (8 in.

TO 12 in.)

HOT

OUTLET

EXPANSION TANK
(OPTIONAL)

MIXING
VALVE

COLD
INLET

CHECK VALVE (IF
USED REQUIRES
EXPANSION TANK)

COLD SUPPLY

HOSE BIB
(OPTIONAL)

FLOW
CONTROL

SUPPLY

RETURN

CHECK
VALVE

EXTERNAL
CIRCULATOR

HYDRONIC
BASEBOARDS
(SERIES CON-
NECTED
SHOWN)

HOT WATER
TO HOUSE
FIXTURE

Figure 15 Combo Heating - Baseboard

C
H

M

WATER
HEATER

200mm TO

300mm (8 in.

TO 12 in.)

HOT

OUTLET

EXPANSION TANK
(OPTIONAL)

MIXING
VALVE

COLD
INLET

CHECK VALVE (IF
USED REQUIRES
EXPANSION TANK)

COLD SUPPLY

HOSE BIB
(OPTIONAL)

FLOW
CONTROL

SUPPLY

RETURN

CHECK
VALVE

EXTERNAL
CIRCULATOR

HYDRONIC
IN-FLOOR
LOOP

HOT WATER
TO HOUSE
FIXTURE

Figure 16 Combo Heating - In-Floor Loop

C
H

M

This manual is related to the following products: