beautypg.com

Installation of the aquastat (temperature control), Electrical supply, National electrical code, ansi/nfpa 70” , (usa) – John Wood Oil-Fired User Manual

Page 14

background image

Installation Of The Aquastat

(Temperature Control)

This heater operates automatically under the control of the
aquastat, which responds to the demand of hot water.
Depending on the model, the aquastat well and wiring is
either installed on the heater, or included in the carton con-
taining the burner. If the installation of the aquastat is
required, proceed as follows:
1. Locate the aquastat well opening in the front of the

heater.

2. Apply a good grade of pipe joint compound to the

threads on the well.

3. Install the well in the tank opening, tighten firmly to

ensure there are no leaks.

4. Insert the sensing bulb of the aquastat into the well and

secure the aquastat to the well using the screw provid-
ed.

5. Wire the control to the burner as shown in the wiring dia-

grams (Figures 9, 10 & 11).

Electrical Supply

General wiring requirements:
Electric shock hazard. Can cause severe personal injury or
death if power source, including service switch on heater, is
not disconnected before installing or servicing. Installations
must comply with the latest editions of these codes:

Canadian Electrical Code Part 1 (CSA C22.1)”
(Canada).

“National Electrical Code, ANSI/NFPA 70”, (USA).

Any additional local, provincial, national or state codes.

Wiring must be N.E.C. Class 1. If original wire supplied with
the heater is to be replaced, TYPE 105°C wire or equivalent
must be used. Supply wiring to heater and additional control
wiring must be 14 GA. or heavier. Provide an electrical
ground as required by codes.

– 14 –

LINE VOLTAGE

THERMOSTAT OR

AQUASTAT®

CONTROL

OIL VALVE

BURNER

MOTOR

IGNITOR

CAD

CELL

LIMIT

TO

REMOTE

ALARM

CIRCUIT

JUMPER

ENVIRACOM™

TERMINAL

L1

LIMIT

L2

VALVE

CAD

CELL

ALARM

T

T3

2

1

VIOLET

WHITE

BLUE

ORANGE

RED

BLACK

YELLOW

YELLOW

BURNER
MOTOR

IGNITOR

R7184

BURNER JUNCTION BOX

Figure 9 Typical Primary Control Wiring

(R7184P).

BLOCKED

VENT

SAFETY
SWITCH

L1 HOT

L2 NEUTRAL

LINE VOLTAGE

THERMOSTAT OR

AQUASTAT®

CONTROL

OIL VALVE

BURNER

MOTOR

IGNITOR

CAD

CELL

LIMIT

TO

REMOTE

ALARM

CIRCUIT

JUMPER

ENVIRACOM™

TERMINAL

L1

L2

VALVE

CAD

CELL

ALARM

T

T3

2

1

VIOLET

WHITE

BLUE

ORANGE

BLACK

YELLOW

YELLOW

BURNER
MOTOR

IGNITOR

R7184

BURNER JUNCTION BOX

Figure 10 Typical Primary Control Wiring

(R7184B).

BLOCKED

VENT

SAFETY
SWITCH

L1 HOT

L2 NEUTRAL

This manual is related to the following products: