5

Model

Fan Motor

hp*

Air Volume

cfm

Fan

RPM

Standard Fan

Motor Frame

Pump Motor

hp

Spray Water

GPM

Sump Heater

kW

Approximate Weight lb

shipping

operating

JW10A

2

5280

689

145T

1

2

40

2.0

910

1400

JW10B

2

5150

706

145T

1

2

40

2.0

955

1400

JW10C

3

5450

825

182T

1

2

40

2.0

1005

1500

JW15B

5

8500

729

184T

1

2

50

2.0

1365

2000

JW15C

5

8300

740

184T

1

2

50

2.0

1435

2400

JW25A

5

11700

500

184T

3

4

70

4.0

1850

2800

JW25B

5

11800

523

184T

3

4

70

4.0

1955

2900

JW25C

7

1

2

13000

614

213T

3

4

70

4.0

2075

3200

JW35A

7

1

2

19000

413

213T

1

110

4.0

2955

4300

JW35B

10

20000

462

215T

1

110

4.0

3140

4600

JW35C

10

19500

476

215T

1

110

4.0

3305

5000

JW50A

15

30200

385

254T

2

150

6.0

4380

6700

JW50B

15

29200

397

254T

2

150

6.0

4635

7200

JW50C

15

28400

385

254T

2

150

6.0

4885

7600

JW70B

20

37200

385

256T

3

250

8.0

6685

10200

JW70C

25

39000

415

284T

3

250

8.0

7085

10900

JW85B

30

52300

415

286T

3

325

11.0

7725

11900

JW85C

30

50000

430

286T

3

325

11.0

8185

12900

JW100B

30

58300

270

286T

5

375

11.0

9170

16870

JW100C

30

61000

280

286T

5

365

11.0

9675

17775

JW115B

40

66000

280

324T

5

400

14.0

10080

19050

JW115C

40

69000

290

324T

5

400

14.0

10670

20170

JW130B

50

76500

300

326T

5

450

16.0

11025

21425

JW130C

50

80000

305

326T

5

450

16.0

11720

22620

* For static pressure from

1

4

to

1

2

ESP use next size larger motor

Model

JWL

Sump Capacity

gal

JW

Coil Volume

gal

JWH

Coil Face Area

sq ft

Circuits

Connection OD

Circuits

Connection OD

Circuits

Connection OD

JW10A

10

2

@

2

5

8

"

43

21

2

@

2

5

8

"

16

9.7

JW10B

21

2

@

2

5

8

"

43

42

2

@

2

5

8

"

20

9.7

JW10C

21

2

@

2

5

8

"

43

42

2

@

2

5

8

"

24

9.7

JW15B

26

2

@

3

1

8

"

64

52

2

@

3

1

8

"

31

14.5

JW15C

26

2

@

3

1

8

"

64

52

2

@

3

1

8

"

37

14.5

JW25A

33

2

@

3

1

8

"

95

66

2

@

3

1

8

"

37

21.6

JW25B

33

2

@

3

1

8

"

95

66

2

@

3

1

8

"

47

21.6

JW25C

33

2

@

3

1

8

"

95

66

2

@

3

1

8

"

57

21.6

JW35A

41

2

@

3

1

8

"

163

82

2

@

3

1

8

"

54

32.5

JW35B

41

2

@

3

1

8

"

163

82

2

@

3

1

8

"

70

164

4

@

3

1

8

"

32.5

JW35C

41

2

@

3

1

8

"

163

82

2

@

3

1

8

"

86

205

4

@

3

1

8

"

32.5

JW50A

50

2

@

3

1

8

"

248

100

2

@

3

1

8

"

82

49.6

JW50B

50

2

@

3

1

8

"

248

100

2

@

3

1

8

"

106

200

4

@

3

1

8

"

49.6

JW50C

50

2

@

3

1

8

"

248

100

2

@

3

1

8

"

130

250

4

@

3

1

8

"

49.6

JW70B

70

4

@

3

1

8

"

374

140

4

@

3

1

8

"

146

280

8

@

3

1

8

"

70.4

JW70C

70

4

@

3

1

8

"

374

140

4

@

3

1

8

"

182

350

8

@

3

1

8

"

70.4

JW85B

70

4

@

3

1

8

"

454

140

4

@

3

1

8

"

177

280

8

@

3

1

8

"

85.5

JW85C

70

4

@

3

1

8

"

454

140

4

@

3

1

8

"

200

350

8

@

3

1

8

"

85.5

JW100B

76

4

@

3

1

8

"

748

152

4

@

3

1

8

"

212

304

8

@

3

1

8

"

92.5

JW100C

76

4

@

3

1

8

"

748

152

4

@

3

1

8

"

262

380

8

@

3

1

8

"

92.5

JW115B

76

4

@

3

1

8

"

880

152

4

@

3

1

8

"

247

304

8

@

3

1

8

"

108.9

JW115C

76

4

@

3

1

8

"

880

152

4

@

3

1

8

"

305

380

8

@

3

1

8

"

108.9

JW130B

76

4

@

3

1

8

"

1012

152

4

@

3

1

8

"

305

304

8

@

3

1

8

"

125.2

JW130C

76

4

@

3

1

8

"

1012

152

4

@

3

1

8

"

349

380

8

@

3

1

8

"

125.2

Note

Inlet and outlet connection sizes shown are standard

copper OD and are sized for nominal flow rates. Actual

sizes should be specified to conform to job requirements.

If special connections are required, such as flanges or

threaded fittings, consult your Recold sales representative.

Connection quantity is total of in and out connections