[8] Model DH400ACDCP Air Duct Smoke Detector Specifications
Description
HVAC air duct mounted ionization or photoelectronic smoke detector for separately powered systems or stand alone sys-
tems. Auxiliary alarm relay contacts provide fan contactor shutdown to prevent HVAC circulation of smoke.
Environmental Limits
Temperature:
32°F to 120°F
0°C to 49°C
Humidity:
10% to 93% R.H. non-condensing
Air Velocity:
500 to 4000 Ft/min.
2.54 to 20.3 m/sec.
Test Features
Magnetic test switch, magnetic reset switch, MOD400R test module (optional), RTS451 Remote Test Station (optional).
Mechanical Specifications
Length:
14.5˝ (37 cm)
Width:
5˝ (13 cm)
Depth (installed):
4˝ (10 cm)
Weight:
4 pounds (1.8 kg)
Terminals
Captive universal terminal screws with sems plates accept wire sizes of 14 gauge or smaller. The screws can withstand 10
in-lbs of tightening torque without damage.
Accessories
MOD400R
Sensitivity Test Module
RA400Z
Remote Annunciator
RTS451/RTS451KEY
Remote Test Station, test & reset switch with alarm LED
PA400
Piezo Sounder
APA451
Annunciator with piezo, alarm & power LEDs
F36-05-00
Replacement Air Filter (two per package)
M02-04-00
Replacement Test Magnet
P48-21-00
Replacement End Plug for inlet sampling tube
R59-18-00
Replacement Calibrated Test Card (For photo units only)
RS24
Replacement Screen, Photo
A2650-01
Replacement Installation Kit (mounting hardware)
Sampling (Inlet) Tubes
TUBE
OUTSIDE DUCT WIDTH
ST-1.5
1 to 2 feet (0.3 to 0.6 m)
ST-3
2 to 4 feet (0.6 to 1.2 m)
ST-5
4 to 8 feet (1.2 to 2.4 m)
ST-10
8 to 12 feet (2.4 to 3.7 m)
Exhaust Tube Extension
A2440-00
5.75 in. (14.6 cm.) additional
Electrical Specifications
Power supply voltage:
20-29 VDC
24 VAC 50-60-Hz
120 VAC 50-60 Hz 220/240 VAC 50-60 Hz
Input capacitance:
270 µF max.
270 µF max.
N/A
N/A
Reset voltage:
3.0 VDC min.
2.0 VAC min.
10 VAC min.
20 VAC min.
Reset time (with RTS451):
.03 to 0.3 sec.
.03 to 0.3 sec.
.03 to 0.3 sec.
.03 to 0.3 sec.
Reset time (by power down):
0.6 sec. max.
0.6 sec. max.
0.6 sec. max.
0.6 sec. max.
Power up time:
34 sec.max.
34 sec. max.
34 sec. max.
34 sec. max.
Alarm response time:
2 to 17 sec.
2 to 17 sec.
2 to 17 sec.
2 to 17 sec.
Sensitivity Test:
See head label
See head label
See head label
See head label