2. defrosting operation (heating) – Sanyo STB1220C1 User Manual
Page 49

45
10-2. Defrosting Operation (Heating)
■
Defrosting Flowchart
■
Defrosting Mode Timing Chart
Once the air conditioner enters defrosting mode, it will not release defrosting until the
outdoor heat exchanger coil temperature rises above 39°F. During this period, heat is
provided by electric heater instead of by the heat pump.
NOTE
Outdoor heat
exch coil
temp.
Release of defrosting
Start of defrosting
39
°
F
14
°
F
ON
Solenoid coil
(4-way valve)
Compressor
OFF
ON
ON
ON
Electric heater
ON
ON
Fan motor
OFF
OFF
Set speed
YES
YES
Temperature of outdoor heat
exchanger coil is blow 14
°
F.
Temperature of outdoor heat
exchanger coil is higher than
39
°
F.
Defrosting begins
Compressor ON
Release of defrosting
NO
NO
●
Compressor
➞
OFF
●
Electric Heater
➞
ON
Heat Pump Model
Model STB0823H1