Siemens BACnet VAV Actuator Owner’s Manual

Siemens Building Technologies, Inc.

25

Descriptor Address

1

Application Description

MTR2 POS

{53}

2560, 2561, 2597

The current position of the Motor 2 actuator in
percent of full travel (for use as an auxiliary slave
point). This value is calculated based on motor run
time. See MTR2 TIMING.

VLV POS

{53}

2565

The current position of the valve in percent of full
travel for applications using a water valve. This
value is calculated based on motor run time.

VLV1 POS

{53}

2563

The current position of valve 1 in percent of full
travel for applications using a water valve. This
value is calculated based on motor run time.

MTR2 TIMING

55

All except

2562, 2564, 2566

The time required for the Motor 2 actuator to travel
from full closed to the full open position.

DMPR ROT ANG

56

All except 2597

The number of degrees the damper is free to travel.

DPR1 ROT ANG

56

2597

The number of degrees that damper 1 is free to
travel.

DPR2 ROT ANG

57

2597

The number of degrees that damper 2, the hot duct
damper, is free to travel.

MTR SETUP

58

All

The configuration setup code for Motors 1, 2, and 3.
This enables the motors individually and sets each
motor to be either direct or reverse acting.

Note: When a motor is enabled, its associated DOs

are enabled.

DO DIR.REV

59

All

The configuration setup code for DOs. Allows the
DOs to be direct or reverse acting (enabled equals
energized or disabled equals de-energized).

EHEAT FLOW

60

2562

The flow required before the electric heat will be
enabled.

COOL TEMP

61

2561

The discharge air temperature where the controller
will switch from heating to cooling mode. Used only
in applications with SUPPLY TEMP.

HEAT TEMP

62

2561

The discharge air temperature where the controller
will switch from cooling to heating mode. Used only
in applications with SUPPLY TEMP.

CLG P GAIN

63

All except 2597

The proportional gain value for the cooling
temperature control loop.

CLG l GAIN

64

All except 2597

The integral gain value for the cooling temperature
control loop.

CLG D GAIN

65

All except 2597

The derivative gain value for the cooling
temperature control loop.

CHK OUT

66

All

The procedure tests all of the necessary I/O and
ensures the controller has the ability to operate
within the set airflow range, between CLG FLOW
MIN and CLG FLOW MAX.

HTG P GAIN

67

All except

2560, 2597

The proportional gain value for the heating
temperature control loop.