beautypg.com

Overview, Fan operation, Siemens bacnet vav actuator owner’s manual – Siemens BACNET 125-5037 User Manual

Page 25: Siemens building technologies, inc. 15

background image

Siemens BACnet VAV Actuator Owner’s Manual

Siemens Building Technologies, Inc.

15

Application 2564 VAV Series Fan Powered with
Electric Reheat

Overview

In Application 2564, the controller modulates the supply air damper of the terminal box for
cooling and controls stages of electric reheat for heating. When in heating, the terminal box
either maintains minimum airflow or modulates the supply air damper. The terminal box also
has a series fan for air circulation. In order for the terminal box to work properly, the central
air-handling unit must provide supply air. See Figure 11.

Fan Operation

CAUTION:

On series fan powered terminal boxes, the terminal box fan must be
controlled/interlocked to start either before or at the same time as the central air
handler. Failure to do so may cause the terminal box fan to rotate backwards and
cause consequent damage at start up.

In day mode, the fan is ON all the time. In night mode, the fan cycles on when heating or
cooling is required.

BACnet Actuator

Controller

Modulating

Damper

Actuator

TEC2564CDR1

Air

Velocity

Sensor

SAFETIES

BY

OTHERS

6

5

4

3

C

Wall Switch (Opt.)

"COMMON" Termination for all DOs

10K ohm Thermistor
or Spare DI

Hi/Lo Tubing

Connections

RTS

FLN

NO

Supply

Air Damper

3 Stage

Electric
Reheat

Supply Air

Recirculated

Plenum Air

Recirculated

Air Damper

3 to 5 Straight Duct Diameters

required for proper sensor reading

Fan

Elec Heat

Stage 3

Electric Heat

Stage 2

Electric Heat

Stage 1

Figure 11. Application 2564 Control Drawing.