beautypg.com

Temperature sensors, Communication wiring, Controller led indicators – Siemens BACNET 125-5037 User Manual

Page 14: Room temperature sensor

background image

Product Overview

4

Siemens Building Technologies, Inc.

Communication Wiring

The controller connects to the field panel by means of a Floor Level Network (FLN)
trunk. Communication wiring connects to the three screw terminals on the controller
labeled “+” (positive), “-“(negative), and “S” (Shield) (Figure 3).

FLN TRUNK

+ -

(SHIELD)

(SHIELD)

(+)

(+)

(-)

(-)

TEC05XXR1

TEC0516R2

Wirenut

120 ohm

½ W

120 ohm

½ W

Note: = System Common

e to earth
Terminator

3-Wire Network Interface

+

-

+

-

+

-

NOTE: When wiring a 3-wire system to a 2-wire system see
the Wiring Guidelines Manual (125-3002) for detailed information.

Figure 3. Communication Wiring (2-wire).

Figure 4. Communication Wiring (3-wire).

Controller LED Indicators

The controller has seven Light Emitting Diode (LED) indicators (see Figure 1).

Table 2. Controller LEDs.

LED Type

Label

(if present)*

LED

Number

Indication

DO

LED 3 - LED 6

3 - 6

Indicates the ON/OFF status of the DO
associated with it. A glowing LED indicates that
the DO is energized.

Transmit

TX

0

Indicates, when flashing, that the controller is
transmitting information to the field panel.

Receive

RX

1

Indicates, when flashing, that the controller is
receiving information from the field panel.

BST

”Basic Sanity Test”

BST

2

Indicates, when flashing ON and OFF once per
second, that the controller is functioning
properly.

* Some LED labels and numerals may be hidden by the controller cover.

Temperature Sensors

Room Temperature Sensor

The controller room temperature sensor connects to the controller by means of a
cable terminated at both ends with a six-conductor RJ-11 plug-in connector.