3

Mounting and installing

3.1 Installation

place

The location of the HP-COMPACT must be driven by the following criteria:

− Protection

from

unauthorized handling

− Dry dust free room, no condensation

− Never install directly over the battery and never in a cabinet together with the

batteries

− Keep ventilation holes free

− In mobile installations it is important to keep the vibrations down as low as

possible

3.2 Fixing

Basically the HP-COMPACT can be installed in any desired location but only
vertically. First of all the plate supplied along with the HP-COMPACT must be
screwed firmly (due to the weight of the device) on the wall. Then the HP-COMPACT
is hooked on the plate and screwed underneath.
Cautious: the fixing must be fully made otherwise the HP-COMPACT may fall
and cause important damages.
In motor vehicles HP-COMPACT must be fixed on vibrations reducing elements. The
HP-COMPACT must not be fixed on a combustible base, as the back of the casing
can get hot and reach up to 60 degrees Celsius.

3.3 Connections

3.3.1 General instructions on connecting

− The cable connection on the terminals AC INPUT and AC OUTPUT must be

carried out with a screwdriver Nr.3 and the connection of the AUX RELAY
terminal with a screwdriver Nr.2.

− The conductor cross section on the terminals AC INPUT / AC OUTPUT / must

comply with the local rules.

− All connecting cables and also the battery cables must be fixed with strain relief

clamps.

− The fuses supplied with the HPC 4400-24, 6000-48 and 8000-48 have to be

installed (see description in 3.4). The cable cross section for the HP 2800-12,
4400-24, 6000-48 and 8000-48 is resp. 95, 70, 50 and 70 mm2 and their length
must be as short as possible (max. 2m).

− The fuse supplied with the product (save for HPC 2800-12) does not protect the

battery cables.

To protect the battery cables, a fuse corresponding to the conductor cross

section must be fixed directly on to the battery.

− All cables must be tightly screwed in place. For safety, a yearly control is

recommended. In mobile installations controls must be carried out more often.

− Connecting must be done by qualified people. Material such as cable,

connectors and distribution boxes, fuses etc. used in the installation must
comply with the respective valid low-voltage installation rules and regulations in
force.

3.3.2 Protection cover of the terminals connections
The protection cover must to be closed after any service on the appliance.

3.4 Connection

Plan