4 auxiliary contact – Studer Innotec HPC 2800-12 User Manual
Page 23
STUDER INNOTEC
HP-COMPACT
HP-COMPACT
V5.4
25/80
5.3.2 Table of voltage and timing threshold
The voltage levels (low voltage, float charge, end of charge and equalization) and the
du-ration of the absorption charge can be changed.
The display of these voltages and the times in the program mode are in accordance
with the diagram shown below:
Low voltage
Float charge
Absorption
Equalization
Absorption
time
Equali-
zation
time
LED
LED 13
LED 12
LED 11
LED 10
LED
10/11/12/13
LED 10/11
12 24 48 12 24 48 12 24 48 12 24 48 12/24/48 12/24/48
14
12.0 24.0 48.0 13.7 27.4 54.8 16.2 32.4 64.8 16.2 32.4 64.8
4h
3h
15
11.8 23.6 47.2 13.6 27.2 54.4 15.6 31.2 62.4 15.9 31.8 63.6
3h
2h
16 11.6 23.2 46.4 13.5 27.0 54.0 15 30 60 15.6 31.2 62.4
2h
1h
17
11.4 22.8 45.6 13.4 26.8 53.6 14.4 28.8 57.6 15.3 30.6 61.2
1h
40’
18
11.2 22.4 44.8 13.3 26.6 53.2 14.2 28.4 56.8 15 30 60
0
–
1’
20’
The heavy printed values show the standard settings.
5.4 Auxiliary
contact
5.4.1 Principle
The Auxiliary Contact can be basically programmed for any operating situation of the
HP-COMPACT which is indicated with a LED. The programming is possible for one
or more operating situations. If the contact is programmed for many situations, it is
activated as soon as the HP-COMPACT finds itself in any one of the programmed
situations. That means that the work of the contact meets that of the logic OR–
Function.
5.4.2 The programming of the Auxiliary Contact
The programming of the Auxiliary Contact is carried out in the following Steps:
− The Push Button 21 (Program) presses down for min. 2 seconds. The LED 4
„Program“ is lit as an indication, that the HP-COMPACT is in program mode.
− A blinking LED shows the programmed condition for the auxiliary contact (LED
10/11/ 12/13 factory setting).
− With the Push Button 20 (select), select the desired condition in which the
contact should be activated.
− With the Push Button 19 (Change status) confirm or change the status for this
condition. If desired, with the Push Button 20 (select) select another condition in
which the contact should be activated.
− With the Push Button 19 (Change status) confirm or change the status for this
condition. If during 30 seconds no buttons are pushed, then the settled values
are automatically stored and the HP-COMPACT switches back to normal
operating condition.
5.4.3 Auxiliary Contact as generator starter
As per the battery capacity
When in the programming of the Auxiliary Contact, the Battery Capacity (LED 15-18)
is used as a condition, you must then take note of the following requirements.
If you have to start an emergency back-up supply with a battery having a certain
residual capacity, then two battery levels must be programmed. The first (i.e. Battery
25% LED 17) for the starting or activating the Auxiliary Contact and the second (i.e.
Battery 100% LED15) for stopping or disabling the Auxiliary Contact. Programmed