Generator sizing guide, Table 5 – lp vapor (lpv) tank sizing – Siemens Standby Generators User Manual

Page 7

background image

Generator Sizing Guide

Table 5 – LP Vapor (LPV) Tank Sizing

Vapor Withdrawal

Tank Capacity

Tank Capacity

Length

Diameter

Overall Ht.

Minimum Temp

Tank Capacity

Total (Gal.)

Useable (Gal.)

(Inches)

(Inches)

(Inches)

(°F)

(btu/hr.)

120

72

57

24

33

40

246,240

20

164,160

0

82,080

150

90

68

24

33

40

293,760

20

195,840

0

97,920

250

150

94

30

39

40

507,600

20

338,400

0

169,200

325

195

119

30

39

40

642,600

20

428,400

0

214,200

500

300

119

37

46

40

792,540

20

528,360

0

264,180

850

510

165

41

50

40 1,217,700
20

811,800

0

405,900

1000

600

192

41

50

40 1,416,960
20

944,640

0

472,320

LP Vapor (LPV) Withdrawal Fuel Consumption

Load (kW)

BTU / Hr

Gal / Hr

7

110,000

1.2

10

190,000

2.1

13

215,000

2.4

16

252,000

2.8

20

340,000

3.8

25

390,000

4.3

35

500,000

5.5

45

620,000

6.8

60

800,000

8.8

70

950,000

10.5

80

1,100,000

12.2

100

1,400,000

15.5

130

1,800,000

19.9

150

2,050,000

22.7

Note: Tank BTU capacity and generator run times based upon maintaining a minimum tank fuel level of 20%.

Note: Fuel consumption based on a generator 80% loaded.

6