Generator sizing guide, Table 3 – surge capability – Siemens Standby Generators User Manual

Page 5

background image

Generator Sizing Guide

Table 3 – Surge Capability

Siemens Liquid Cooled Generators Operating at <3600 RPM

Rated Output

Surge Capability

Surge Capability

(Running Amps)

LR Amps at 15% Voltage Dip

LR Amps at 30% Voltage Dip

Size (kW)

240V 1ø

208V 3ø

480V 3ø

240V 1ø

208V 3ø

480V 3ø

240V 1ø

208V 3ø

480V 3ø

25

104

87

38

71

47

26

133

89

52

70

292

243

105

275

183

106

550

366

212

80

333

278

120

275

183

106

550

366

212

100

417

347

150

371

247

142

738

491

284

130

542

451

195

546

364

209

1088

724

419

Siemens Generators Operating at 3600 RPM

Rated Output

Surge Capability

Surge Capability

(Running Amps)

LR Amps at 15% Voltage Dip

LR Amps at 30% Voltage Dip

Size (kW)

240V 1ø

208V 3ø

480V 3ø

240V 1ø

208V 3ø

480V 3ø

240V 1ø

208V 3ø

480V 3ø

7

29

24

11

23

n/a

n/a

46

n/a

n/a

10

42

35

15

31

n/a

n/a

63

n/a

n/a

13

54

45

20

38

n/a

n/a

75

n/a

n/a

16

67

56

24

46

n/a

n/a

92

n/a

n/a

20

83

69

30

63

42

24

121

80

47

25

104

87

38

71

47

26

138

92

53

35

146

121

53

104

69

40

204

136

78

45

188

156

68

146

97

57

292

194

112

60

250

208

90

179

119

69

354

236

136

70

292

243

105

246

164

95

496

330

190

100

417

347

150

333

222

128

663

441

255

150

625

520

226

558

372

215

1121

747

431

4

Note: All kW models listed above are based on nominal LP rating.