beautypg.com

Generator sizing guide, Table 1 – motor load reference – Siemens Standby Generators User Manual

Page 3

background image

Generator Sizing Guide

Table 1 – Motor Load Reference

AC and Heat Pumps

Running Load

Starting Load

Running Amps at Amps at

Amps at

Starting

LR Amps

LR Amps

LR Amps

Description

Hp

kW

240V 1ø

208V 3ø

480V 3ø

kW

at 240V 1ø

at 208V 3ø at 480V 3ø

1 Ton (12,000 BTU)

1

1

5

3

1

3

25

17

7

2 Ton (24,000 BTU)

2

2

10

7

3

6

50

33

14

3 Ton (36,000 BTU)

3

3

15

10

4

9

75

50

22

4 Ton (48,000 BTU)

4

4

20

13

6

12

100

67

29

5 Ton (60,000 BTU)

5

5

25

16

7

15

125

83

36

7.5 Ton (85,000 BTU)

7.5

7.5

37

24

11

17

188

125

54

10 Ton (120,000 BTU)

5 Hp (x2)

10

49

33

14

15

125

83

36

10 Ton (120,000 BTU)

10 Hp

10

49

33

14

20

250

167

72

15 Ton (180,000 BTU)

7.5 Hp (x2)

15

74

49

21

17

188

125

54

15 Ton (180,000 BTU)

15 Hp

15

74

49

21

30

375

250

108

20 Ton (240,000 BTU)

10 Hp (x2)

20

98

65

28

20

250

167

72

20 Ton (240,000 BTU)

20 Hp

20

n/a

65

28

40

500

333

144

25 Ton (300,000 BTU)

25

25

n/a

82

35

50

625

416

180

30 Ton (360,000 BTU)

15 Hp (x2)

30

n/a

98

42

30

375

250

108

30 Ton (360,000 BTU)

30 Hp

30

n/a

98

42

60

750

500

217

40 Ton (480,000 BTU)

20 Hp (x2)

40

n/a

131

57

40

500

333

144

40 Ton (480,000 BTU)

40 Hp

40

n/a

131

57

80

1000

666

289

50 Ton (480,000 BTU)

25 Hp (x2)

50

n/a

163

71

50

625

416

180

50 Ton (480,000 BTU)

50 Hp

50

n/a

163

71

100

1250

833

361

General Residential

Running Load

Starting Load

Running

Amps at

Amps at

Starting

LR Amps

LR Amps

Description

Hp

kW

120V 1ø

240V 1ø

kW

120V 1ø

240V 1ø

Refrigerator, Sump Pump,

0.5

0.5

4.9

2.5

1.5

25

13

Furnace, Garage Opener

Freezer, Washer, Septic Grinder

0.75

0.75

7.4

3.7

2.3

38

19

General 1 Hp

1

1

9.8

4.9

3

50

25

Well and Septic Lift Pump

2

2

19.6

9.8

6

100

50

2