Flue installation for the 705 model – State Models: 305 User Manual
Page 29
![background image](/manuals/138094/29/background.png)
305, 505, 705 Indoor Manual
29
Vertical Terminations
The air intake requires a return bend or two 90º elbows to prevent entry of rain.
SLOPE INTAKE AND EXHAUST
TOWARD OUTSIDE TERMINATION
MINIMUM 1/4" PER FOOT
Horizontal with Concentric Termination
Flue
Installation
for
the
705
Model
The vent termination and air intake must be in the same pressure zone.
12” MIN. ABOVE
GRADE OR
SNOW LEVEL
3”
MAX
12” MIN
12”
MIN
COMBUSTION
AIR PIPE
EXHAUST PIPE
ANTICIPATED
SNOW LEVEL
3”
3”
MAX
12” MIN
12” MIN
3”
MAX
12” MIN
12” MIN
This manual is related to the following products:
See also other documents in the category State Water boiler:
- GPH-90N (60 pages)
- GPH-90N (63 pages)
- GP6 50 YTPDT (4 pages)
- GP6 50 YTVIT (40 pages)
- GS6 40 YBFT (40 pages)
- Series 300 (40 pages)
- GP 6 40YPC T 100 (40 pages)
- GS6 30 UORT (36 pages)
- GS6 75 URRBS (24 pages)
- GS6 75 URRBS (32 pages)
- GS6 30 YOCT (24 pages)
- GS6 30 YOCT (36 pages)
- GS6 40 YBPDT (36 pages)
- PR6 40 XBPDT (36 pages)
- GS6 40 YBVIT (32 pages)
- GS6 40 YBVIS (60 pages)
- GS6 75 YRVIT (36 pages)
- PR6 40 XCVIT (20 pages)
- PR6 40 XRVIT (40 pages)
- PR6 30 NOMT (24 pages)
- PR6 30 NHDST2 (32 pages)
- PR6 50 NHDST2 (28 pages)
- GS6 40 YBDS (48 pages)
- PR6 40 XODS (44 pages)
- GS6 65 XRRT (24 pages)
- GS6 75 XRRS (24 pages)
- GS6 30 YOMT (32 pages)
- GP6 50 YTPDT (60 pages)
- GP6 50 HTPDT (56 pages)
- EPX 60 DHPT (22 pages)
- SPX 50 DHPT (20 pages)
- HPWH Inlet/Outlet Duct (3 pages)
- EPX 40 DXRT (28 pages)
- P6 30 20T1 (20 pages)
- P6 6 10 MS K (20 pages)
- ES6 2 SSUS K (20 pages)
- MHEW2-30L-035D (16 pages)
- SCI 30 DHMS (24 pages)
- SBN71 120NE thru (52 pages)
- SDV 75 70 NE/PE (40 pages)
- SDV 75 70 NE/PE (36 pages)
- SBS65 65NE (24 pages)
- SBS75 76NE (36 pages)
- SBB75 76NE (24 pages)
- GPG/GPV-540A (37 pages)