Sentry switched cdu, Cw-24vd/y, Key features – Server Technology VY-3PH User Manual
Page 2: High-density power distribution, Additional benefits, Single web interface, Branch circuit protection, Input current monitoring, Temperature and humidity, Additional features and specifications
Model
Available Input
Voltages
Outlets
Available Input
Cord
Amperage
Dimensions**
(L x W x D)
© Server Technology, Inc. 10/2007 version. Information in this document is subject to change without notice. Sentry is a trademark of Server Technology, Inc. Patent # 7,043,543. Patent Pending. Printed in US.
Sentry : Solutions for the Data Center Equipment Cabinet
Key Features
Sentry : CDU Technical Specifications
Sentry Switched CDU
CW-24VD/Y
High-Density Power Distribution
The Switched CDU’s combine remote configuration and management
with power distribution and power and environmental monitoring.
Reboot a single or dual-power server with one command. Receive
SNMP-based alerts and email alerts when power or environmental
conditions exceed thresholds. Assign users specific access rights to
designated outlets or groups.
Only the Switched CDU products provide the flexibility needed for all
data centers and remote sites, including power requirements for
high-amp, high voltage; UL 60950-1 branch circuit protection; SSL &
SSH security; and SNMP-based input current monitoring.
The Switched CDU also supports Enterprise View PDU Manager.
This gives the engineer the ability to manage a large installation of
Networked CDUs from one location, view and access multiple Smart
and Switched CDUs from a
single web interface.
> Remote Power Management:
Power cycle individual power
outlets, or groups of power
outlets, to remotely reboot
servers and network devices,
anywhere in the world. Or,
power-off unused power
receptacles
> High Power Distribution:
3-Phase power; 20 or 30-Amp
power input feed options
> High Density: Single power
input feed; 24 outlets per
enclosure
> IP Access & Security: Web
interface, SSL, SSH, Telnet, SNMP,
FTP, SNTP, Syslog, LDAP, LDAPS,
TACACS
and RS-232 access
> Add an Expansion Module:
Daisy chain the Switched CDU
Expansion Module (CW/CX) for
power management of separate
power circuits from a single IP
address
> Environmental Monitoring:
Each Switched CDU supports two
temperature & humidity probes
and reports conditions thru the
Web interface
> Enterprise View: View and
access multiple Switched CDUs
from one Web interface**
> SNMP Traps: Provide automated
alerts for power and
environmental conditions
> Input Current Monitor:
Precisely measure the aggregate
current draw (in amps) on each
power circuit. On-site verification
of the input current with the LED
digital display. Remote
verification via browser or serial
screen.
> Power-up Sequencing: Prevent
an in-rush power overload
Branch Circuit Protection
The Sentry CDU Family meets the new UL 60950-1
requirement for branch circuit protection.
Attention!
The Sentry CDU products meet the above criteria by
providing overcurrent protection with UL-listed Bussman SC fuses for
each branch circuit.
Input Current Monitoring
The CDU’s exclusive True RMS current monitoring is critical
to preventing overloads in high-density computing
environments. LED digital displays on the CDU enclosure
report the input current of each phase or branch circuit.
Temperature and Humidity
The Switched CDU supports two external probes. Each of
these probes measure both temperature and humidity.
Receive SNMP-based alert notifications when conditions
exceed defined thresholds.
Additional Benefits:
CW-24V2-C20M
CW-24VY-L20M*
CW-24V2-L30M
CW-24VY-L30M*
208-240V
50/60Hz
208-240V
50/60Hz
3-Phase Wye, 208V
50/60Hz
3-Phase Wye, 208V
50/60Hz
30A
20A
30A
20A
IEC 60320/C20
Power Inlet
NEMA L6-30P
Cordset
NEMA L21-20P
Cordset
NEMA L21-30P
Cordset
(24) IEC 60320/C13*
(24) IEC 60320/C13*
69.0” x 1.75” x 2.25”
69.0” x 1.75” x 2.25”
69.0” x 1.75” x 2.25”
69.0” x 1.75” x 2.25”
Additional Features and Specifications
Branch Circuit Protection
> Compliant to UL 60950-1
Agency Approvals
> US & Canada (cTUVus mark) to UL 60950-1:2003 and
CAN/CSA 22.2 No. 60950-1-03
> European Union (TUVGS mark) to EN 60950-1:2001
> FCC Class A, Part 15
> CE
> EMC - EN 55022 Class A, EN 55024
Communications and Security
> 10/100 BaseT Ethernet
> HTTP/HTTPS
> SSLv3/TLSv1
> SNMPv2
> SSHv2
> Telnet
> LDAPv3
> LDAPS
> TACACS+
> RS-232 (Serial)
Accessories
> Optional Temperature & Humidity Probe
EMTH-1-1 Temperature & Humidity Probe, 10’
Power Cord Options
> PTCORD-1 IEC 60320/C19 - NEMA L6-20P , 10’
> PTCORD-2 IEC 60320/C19 - Schuko 10’
> PTCORD-3 IEC 60320/C19 - IEC 60309 (BS4343, CEE17)
16/20A Blue (UK Commando) 10’
> PTCORD-4 IEC 60320/C19 - BS1363 13A (UK) 10’
> PT-ADP-C19 Cable mount IEC 60320/C19 Connector
**Enterprise View sold separtely
Expansion Module
Model Numbers
> CX-24VD-L20M
> CX-24VD-L30M
> CX-24VY-L20M
> CX-24VY-L30M
(24) IEC 60320/C13
(24) IEC 60320/C13
CW-24VE-C20M
CW-24VE-P32M
230V
50/60Hz
230V
50/60Hz
32A
16A
IEC 60320/C20
Power Inlet
IEC 60309
Cordset
69.0” x 1.75” x 2.25”
69.0” x 1.75” x 2.25”
(24) IEC 60320/C13
(24) IEC 60320/C13
*This unit has an additional NEMA 5-20R, 110V Utility Outlet
**Please note that the depth of these enclosures are 3.0” deep at the placement of the fuse retractors
CW-24VD-L20M
CW-24VD-L30M
3-Phase Delta, 208V
50/60Hz
3-Phase Delta, 208V
50/60Hz
30A
20A
NEMA L15-20P
Cordset
NEMA L15-30P
Cordset
(24) IEC 60320/C13
(24) IEC 60320/C13
69.0” x 1.75” x 2.25”
69.0” x 1.75” x 2.25”
Ex
M
>
>
>
>