beautypg.com

Server Technology CW-8H User Manual

Sentry switched cdu, Cw-8h, Key features

background image

Model

Available Input

Voltages

Outlets

Available Input

Cord

Amperage

Dimensions*

(L x W x D)

Sentry : Solutions for the Data Center Equipment Cabinet

Key Features

Sentry : CDU Technical Specifications

Sentry Switched CDU

CW-8H

High-Density Power Distribution

The Switched CDU’s combine remote configuration and management with power
distribution and power and environmental monitoring. Reboot a single or
dual-power server with one command. Receive SNMP-based alerts and email alerts
when power or environmental conditions exceed thresholds. Assign users specific
access rights to designated outlets or groups.

Only the Switched CDU products provide the flexibility needed for all data centers
and remote sites, including power requirements for high-amp, high voltage; UL
60950-1 branch circuit protection; SSL & SSH security; and SNMP-based input current
monitoring.

> Remote Power Management:

Power cycle individual power

outlets, or groups of power

outlets, to remotely reboot

servers and network devices,

anywhere in the world. Or,

power-off unused power

receptacles

> High Power Distribution: 120V,

208V, or 230V power; 20 or

30-Amp power input feed

options

> High Density: Single power

input feed; 8 outlets per 1U

enclosure

> IP Access & Security: Web

interface, SSL, SSH, Telnet, SNMP,
FTP, SNTP, Syslog, LDAP, LDAPS,
TACACS

and RS-232 access

> Add an Expansion Module:

Daisy chain the Switched CDU

Expansion Module (CW/CX) for

power management of separate

power circuits from a single IP

address

> Environmental Monitoring:

Each Switched CDU supports two

temperature & humidity probes

and reports conditions thru the

Web interface

> SNMP Traps: Provide automated

alerts for power and

environmental conditions

> Input Current Monitor:

Precisely measure the aggregate

current draw (in amps) on each

power circuit. On-site

verification of the input current

with the LED digital display.

Remote verification via browser

or serial screen.

> Power-up Sequencing: Prevent

an in-rush power overload

Branch Circuit Protection

The Sentry CDU Family meets the new UL 60950-1
requirement for branch circuit protection.
Attention!

The Sentry CDU products meet the above criteria by

providing overcurrent protection with UL-listed Bussman SC fuses for
each branch circuit. The CW-8H contains fuses within the enclosure.

Input Current Monitoring

The CDU’s exclusive True RMS current monitoring is critical
to preventing overloads in high-density computing
environments. LED digital displays on the CDU enclosure
report the input current of each phase or branch circuit.

Temperature and Humidity

The Switched CDU supports two external probes. Each of
these probes measure both temperature and humidity.
Receive SNMP-based alert notifications when conditions
exceed defined thresholds.

Additional Benefits:

CW-8H1-C20

CW-8H2-C20

CW-8H1-L530

CW-8H2-L630

100-120V

50/60Hz

100-120V

50/60Hz

208-240V

50/60Hz

208-240V

50/60Hz

30A

20A

30A

20A

IEC 60320/C20

Power Inlet

NEMA L5-30P

Cordset

IEC 60320/C20

Power Inlet

NEMA L6-30P

Cordset

(8) NEMA 5-20R

(8) IEC 60320/C13

(8) NEMA 5-20R

(8) IEC 60320/C13

17.0” x 1.75” x 7.0”

17.0” x 1.75” x 7.0”

17.0” x 1.75” x 7.0”

17.0” x 1.75” x 7.0”

Additional Features and Specifications

Branch Circuit Protection

> Compliant to UL 60950-1

Agency Approvals

> US & Canada (cTUVus mark) to UL 60950-1:2003 and

CAN/CSA 22.2 No. 60950-1-03

> European Union (TUVGS mark) to EN 60950-1:2001

> FCC Class A, Part 15

> CE

> EMC - EN 55022 Class A, EN 55024

Communications and Security

> 10/100 BaseT Ethernet

> HTTP/HTTPS

> SSLv3/TLSv1

> SNMPv2

> SSHv2

> Telnet

> LDAPv3

> LDAPS

> TACACS+

> RS-232 (Serial)

Accessories

> Optional Temperature & Humidity Probe

EMTH-1-1 Temperature & Humidity Probe, 10’

Power Cord Options

> PTCORD-1 IEC 60320/C19 - NEMA L6-20P , 10’

> PTCORD-2 IEC 60320/C19 - Schuko 10’

> PTCORD-3 IEC 60320/C19 - IEC 60309 (BS4343, CEE17)

16/20A Blue (UK Commando) 10’

> PTCORD-4 IEC 60320/C19 - BS1363 13A (UK) 10’

> PTCORD-5 IEC 60320/C19 - 5-15P (15A Straight-Blade) 10’

> PTCORD-6 IEC 60320/C19 - 5-20P (20A Straight-Blade) 10’

> PTCORD-7 IEC 60320/C19 - L5-20P (20A Twist-Lock) 10’

> PT-ADP-C19 Cable mount IEC 60320/C19 Connector

**Enterprise View sold separtely

Expansion Module
Model Numbers
> CX-8H1-C20
> CX-8H1-L530
> CX-8H2-C20
> CX-8H2-L630
> CX-8HE-C20

CW-8HE-C20*

230V

50/60Hz

16A

IEC 60320/C20

Power Inlet

(8) IEC 60320/C13

17.0” x 1.75” x 7.0”

*European Model

© Server Technology, Inc. 7/2007 version. Information in this document is subject to change without notice. Sentry is a trademark of Server Technology, Inc. Patent # 7,043,543. Patent Pending. Printed in US.