Johnson Controls XP-910x User Manual
Page 5

Configuration Guides—XT-9100 Configuration Guide 5
XP9103
DO 1
DO 2
DO 3
DO 4
DO 5
DO 6
DO 7
DO 8
XP9102
ADDRESS
A B C
A B C
RD
TD
Power
RS485
FU S E
HOT GND NEUT
E X P
E X P
F U S E
min
max
XT9100
TR9100
E X P
E X P
max
AO7
AO8
min
E X P
Bus Connector (provided)
emtxt-4
D O 5 D O 6 D O 7 D O 8
A I5 A I6 V
AO 7
A O 8
2 4 V
C
2 4 V
C O M
2 4 V
C O M
DO1
DO2
DO3
DO4
+ 1 5 V
A I 1 A I 2 A I 3 A I 4
XT
XP1
XP2
TR
Figure 2: Typical XT-9100 Configuration
Table 2: XT Configurations
TR
Transformer
TR-9100
(optional)
XT
Processor
XT-9100
XP1
Analog
or
Digital
XP-9102
XP-9103
XP-9104
XP-9105
1 or 2 x XP-9106
(See Note 1.)
(See Notes 2 and 4.)
XP2
Digital
XP-9103
XP-9104
XP-9105
1 or 2 x XP-9106
(optional)
(optional)
(optional)
(optional) (See Notes 2, 3, and 4.)
Notes:
1.
The analog XP-9102 must be placed in position XP1.
2.
Two XP-9106 modules are considered as one XP module when installed next to each
other in Position XP1 or XP2. When a single XP-9106 is installed in Position XP1 and
another type of XP module is installed in Position XP2, the total number of I/Os is
restricted to 12.
3.
The XP-9106 can only be placed in Position XP2 when Position XP1 is filled by an
analog XP or two XP-9106 modules.
4.
The first XP-9106 in position XP1 or XP2 controls points DO1-DO4 and the second
XP-9106 in either position controls points DO5-DO8.
5.
Digital modules with counters must be in position XP1.