Johnson Controls XP-910x User Manual
Page 37

Configuration Guides—XT-9100 Configuration Guide 37
RI.
HI.
Type
R/W
Tag
Description
128
80
2 Bytes
CNF
AIT6
Input Type of Analog Input 6
(bits as AIT1)
129
81
Number
CNF
HR6
High Range Analog Input 6
130
82
Number
CNF
LR6
Low Range Analog Input 6
131
83
Number
R/W (E)
HIA6
High Alarm Limit Analog Input 6
132
84
Number
R/W (E)
LOA6
Low Alarm Limit Analog Input 6
133
85
Number
R/W (E)
ADF6
Differential on Alarm Limit [units]
134
86
Number
CNF
FTC6
Filter Constant Analog Input 6
135
87
2 Bytes
Spare
136
88
2 Bytes
CNF
AIT7
Input Type of Analog Input 7
(bits as AIT1)
137
89
Number
CNF
HR7
High Range Analog Input 7
138
8A
Number
CNF
LR7
Low Range Analog Input 7
139
8B
Number
R/W (E)
HIA7
High Alarm Limit Analog Input 7
140
8C
Number
R/W (E)
LOA7
Low Alarm Limit Analog Input 7
141
8D
Number
R/W (E)
ADF7
Differential on Alarm Limit [units]
142
8E
Number
CNF
FTC7
Filter Constant Analog Input 7
143
8F
2 Bytes
Spare
144
90
2 Bytes
CNF
AIT8
Input Type of Analog Input 8
(bits as AIT1)
145
91
Number
CNF
HR8
High Range Analog Input 8
146
92
Number
CNF
LR8
Low Range Analog Input 8
147
93
Number
R/W (E)
HIA8
High Alarm Limit Analog Input 8
148
94
Number
R/W (E)
LOA8
Low Alarm Limit Analog Input 8
149
95
Number
R/W (E)
ADF8
Differential on Alarm Limit [units]
150
96
Number
CNF
FTC8
Filter Constant Analog Input 8
151
97
2 Bytes
Spare