28 Configuration Guides—XT-9100 Configuration Guide
RI.
HI.
Type
R/W
Tag
Description
10
0A
1 Byte
R
DIS2
Digital Input Status XP2
X8 X7 X6 X5 X4 X3 X2 X1
X1 = 1
XP2 : Digital Input 1 is On
X2 = 1
XP2 : Digital Input 2 is On
X3 = 1
XP2 : Digital Input 3 is On
X4 = 1
XP2 : Digital Input 4 is On
X5 = 1
XP2 : Digital Input 5 is On
X6 = 1
XP2 : Digital Input 6 is On
X7 = 1
XP2 : Digital Input 7 is On
X8 = 1
XP2 : Digital Input 8 is On
11
0B
2 Byte
R
AIS
Analog Input Status
X16 X15 X14 X13 X12 X11 X10 X9 X8
X7 X6 X5 X4 X3 X2 X1
X1 = 1
AIH1
High Alarm Condition
X2 = 1
AIL1
Low Alarm Condition
X3 = 1
AIH2
High Alarm Condition
X4 = 1
AIL2
Low Alarm Condition
X5 = 1
AIH3
High Alarm Condition
X6 = 1
AIL3
Low Alarm Condition
X7 = 1
AIH4
High Alarm Condition
X8 = 1
AIL4
Low Alarm Condition
X9 = 1
AIH5
High Alarm Condition
X10= 1
AIL5
Low Alarm Condition
X11= 1
AIH6
High Alarm Condition
X12= 1
AIL6
Low Alarm Condition
X13= 1
AIH7
High Alarm Condition
X14= 1
AIL7
Low Alarm Condition
X15= 1
AIH8
High Alarm Condition
X16= 1
AIL8
Low Alarm Condition