beautypg.com

0 electrical wiring instructions, Electrical wiring instructions, Danger – Jacuzzi J - 230 User Manual

Page 20

background image

J-200 Series

7.0

electrical wiring Instructions

ImporTanT noTICe: The electrical wiring of this spa
must meet the requirements of the National Electrical
Code/USA (NEC) and any applicable state or local codes.
The electrical circuit must be installed by a qualified electrician and
approved by a local building/electrical inspection authority.

1. Convertible 120/240V Power Models:

!

DanGer:

to DeCrease the risk oF shoCk,

proDuCT DamaGe or eleCTrICal FIre.

120v “plug-in” operation: This spa must operate on the supplied

120V GFCI cord at its original length or must be hard-wired for longer

runs. NEVER USE AN EXTENSION CORD FOR ANY REASON!

Convertible 120/240v heater operation:

The included 120V

GFCI cord must be discarded for 240V heater operation. This spa

must be hard wired. Supplying power to either configuration above

which is not in accordance with these instructions will void both the

independent testing agency listing and the manufacturer’s warranty.

2. Dedicated 230V-240V models must be permanently connected

(hard-wired) to the power supply. No plug-in connections or

extension cords are to be used in conjunction with the operation

of this spa. Supplying power to the spa which is not in accordance

with these instructions will void both the independent testing agency

listing and the manufacturer’s warranty.

3. The power supplied to this spa must be a dedicated circuit with no

other appliances or lights sharing the power provided by the circuit.

4. To determine the current, voltage and wire size required, refer to

section 6.0 “Power Requirements” (page 13).

Wire size must be appropriate per NEC/USA and/or local codes.

We recommend type THHN wire.

All wiring must be copper to ensure proper connections.

Do not use

aluminum wire.

When using wire larger than #6 (10 mm²), add a junction box near

the spa and reduce to short lengths of #8 (8.4 mm²) wire to connect

to the spa.

5. The electrical supply for this product must include a suitably rated

switch or circuit breaker to open all ungrounded supply conductors

to comply with Section 422-20 of the National Electrical Code/USA,

ANSI/NFPA 70. The disconnecting means must be readily accessible

to the spa’s occupant but installed at least 5 feet (1.5m) from spa

water.

6. The electrical circuit supplied for the spa must include a suitable

ground fault circuit interrupter (GFCI) as required by NEC/USA Article

680-42.

7. To gain access to the spa’s power terminal block, remove the screws

securing the synthetic cabinet panel under the control panel (Figure A).

16

This manual is related to the following products: