beautypg.com

IDEAL INDUSTRIES CLASSIC HE18 User Manual

Page 37

background image

classic HE -

Installation & Servicing

37

SERVICING

67 PILOT BURNER REPLACEMENT

1. Refer to Frame 61.

2. Remove the burner and air box assembly. Refer to Frame

54.

3. Remove the electrode retaining nut and remove the pilot

shield and electrode.

4. Unscrew the central pilot fixing screw and lift the pilot clear

of the pilot injector. The pilot injector may now be unscrewed
if required.

5. Replace the pilot burner (injector if necessary) and retain

with the M4 screw previously removed. Ensure the copper
sealing washer is replaced when refitting the pilot injector.

6. Replace the electrode and pilot shield, retaining

both with the electrode nut. Check the spark gap.

7. Reassemble in reverse order.

8. Check the operation of the boiler.

9. The pilot is factory set to maximum and no further

adjustment is possible. Ensure there is an inlet
pressure of 20 mbar available. Also check burner
ignition and cross-lighting.

1. Refer to Frame 61.
2. Remove the limit thermostat assembly from the

boiler flow pipe.

3. Disconnect the electrical connectors
4. Clip new thermostat onto flow pipe
5. Reassemble in reverse order.
NOTE. UNDER NO CIRCUMSTANCES REFIT THE
LIMIT THERMOSTAT ONTO THE RETURN PIPE

65 LIMIT THERMOSTAT REPLACEMENT

1. Refer to Frame 61.
2. Pull off the two electrical connections.
3. Remove the two nuts retaining the flue protection

thermostat.

4. Replace the thermostat and re-assemble in reverse

order

66 FLUE PROTECTION THERMOSTAT REPLACEMENT

2

3

2

3

Return pipe

Flow pipe

SER

VICING

201850-6.pmd

21/02/2008, 12:58

37

This manual is related to the following products: