Continuous Flow Icemaker Service Manual

© 2006, IMI Cornelius Inc.

- 11 -

Publication Number: 630460324SER

GEARMOTOR

OVERLOAD TRIPPED

Check water level control

and evaporator water tube

for line build-up restrictions.

Clear ice from

evaporator and

auger before

resetting overload.

CLEAN

CAUTION

See Instructions.

Overload

hot try
again.

YES

NO

Reset overload.

Resets but

motor does

not run.

Will not

Reset.

Icemaker

runs.

IMPORTANT

Will not

reset.

Replace

overload.

Resets but

motor does

not run.

Check

gearmotor

circuits.

Short run. Trips

again in 2

minutes. Check

gearmotor circuits.

Icemaker runs when

reset but problem has

not been found.

Continue checking for
overload as follows to

guard against future

problems.

OVERLOAD GUIDE
ELECTRICAL:

High or low voltage. Weak power lines can cause overloads on icemakers restarts.
High running current (2.4amps or above). Check motor circuits and start relay.

Auger delay failed.

ICEMAKER

Mechanical parts worn. Scored evaporator or auger. Worn thrust bearing.

Icemaker not turning off. Failed ice level control.

Over compression. Low water inlet temperature. Restrictions in water line from reservoir.

REFRIGERANT

Contaminated charge or bad compressor.

Low charge or gas leak.

Low suction pressure. Improper expansion valve. Sensing bulb location or insulation
and/or defective expansion valve.