B-VENT PIPE SIZING

BBV400/400BBV

SBV400/400SBV

SBV500/500SBV

4"

6"

6"

VENT INSTALLATION

INSTALLATION PLANNING

“B” VENT PIPE
See venting installation instructions provided by the B-Vent manufacturer.
Note: This APPLIANCE MUST BE INSTALLED using “B” vent type pipe that has been listed by a

nationally recognized testing agency.

See B-Vent Pipe Sizing chart for proper elbow offset runs.

Locate chimney center line dimension from a combustible back wall. See Figures 3 and 4, page 9.

• Minimum vertical chimney height - 8'

• Minimum height with two (2) 90° elbows - 8'

• Elbow requirements allow a maximum of two (2) 90° elbows or four (4) 45° elbows per installation.

Note: Two (2) 45° elbows = One (1) 90° elbow

• Horizontal run must never exceed 50% of the height of the vent system.