DCA-400SSV— OPERATION AND PARTS MANUAL — REV. #0 (04/19/06) — PAGE 37

1

DCA-400SSV— GENERATOR START-UP PROCEDURE (MANUAL)

Figure 46. Voltage Adjust Control Knob

Figure 47. Ammeter

(No Load)

8. The ammeter (Figure 47) will

indicate

zero amps with no load

applied. When a load is applied, the
ammeter will indicate the amount of
current that the load is drawing from
the generator.

7. The generator's AC-voltmeter (Figure 45) will display the

generator’s output in VOLTS. If the voltage is not within
the specified tolerance, use the voltage adjustment
control knob (Figure 46) to increase or decrease the
desired voltage.

Figure 46. Voltmeter

Figure 44. Frequency Meter (Hz)

6. The generator's frequency meter (Figure 44) should be

displaying the 60 cycle output frequency in HERTZ.

Figure 50. Engine

Tachometer Gauge

11. The

tachometer gauge (Figure 50)

will indicate the speed of the engine
when the generator is operating.
Under normal operating conditions
this speed is approximately 1600
RPM’s.

10. The

coolant temperature gauge

(Figure 49) will indicate the
coolant temperature. Under
normal operating conditions the
coolant temperature should be
between 165 and 203 degrees
Fahrenheit (

Green Zone).

Figure 49. Coolant

Temperature Gauge

9. The engine oil pressure gauge

(Figure 48) will indicate the oil
pressure

of the engine. Under

normal operating conditions the oil
pressure is approximately 44 to 73
psi. (303~503 kPa). When starting
the genera

Figure 48. Oil

Pressure Gauge

Figure 51. Main, Aux. and GFCI

Circuit Breakers (ON)

12. Place the

main, GFCI, and aux. circuit breakers in the

ON position (Figure 51).

13. Observe the generator's ammeter

(Figure 52) and verify it reads the
anticipated amount of current with
respect to the load. The ammeter
will only display a current reading if
a load is in use.

Figure 52. Ammeter

(Load)

14. The generator will run until manually stopped or an

abnormal condition occurs.