Performance data – hoods, Heater parts from acf greenhouses – Modine Manufacturing BAE User Manual
Page 17

Model
BAE 50
BAE 75
BAE 100 BAE 125 BAE 145 BAE 175 BAE 200 BAE 225
BAE 250
BAE 300
BAE 350
BAE 400
X Y Z
X Y Z
X Y Z
X Y Z
X Y Z
X Y Z
X Y Z
X Y Z
X Y Z
X Y Z
X Y Z
X Y Z
8'
11 24 33
16 35 48 16 35 48 21 44 60 23 46 63 21 43 59 25 50 69 26 53 71 29 58 79
30 61 83
36 71 97
36 71 97
10'
9 22 30
15 34 46 15 34 46 20 43 59 21 46 62 20 42 58 24 50 68 25 52 70 28 57 78
29 60 82
35 71 96
35 70 96
12'
7 18 25
14 32 44 14 32 44 19 42 57 20 44 60 18 41 56 22 49 66 23 51 69 26 56 77
28 59 81
34 70 95
34 70 95
14'
–
12 29 41 12 29 41 17 40 55 19 43 59 17 39 54 21 47 65 22 49 68 25 55 75
27 58 80
33 69 94
33 69 94
16'
–
10 26 36 10 26 36 16 38 52 17 41 56 16 37 51 20 45 62 21 48 66 24 54 74
26 57 78
32 68 93
31 68 93
18'
–
–
–
14 35 49 16 38 53 14 34 48 18 43 60 19 46 63 23 52 71
24 56 76
30 67 92
30 67 91
20'
–
–
–
12 31 43 14 35 49 11 30 42 16 41 56 18 43 60 21 50 69
23 54 74
29 65 90
29 65 89
22'
–
–
–
–
–
–
14 37 52 16 40 56 18 48 66
21 51 71
28 64 88
27 63 87
24'
–
–
–
–
–
–
10 29 42 13 35 50 17 44 62
20 49 68
26 62 85
26 61 85
26'
–
–
–
–
–
–
–
–
15 40 56
17 45 63
25 59 82
24 59 82
28'
–
–
–
–
–
–
–
–
11 32 46
14 39 56
23 57 79
23 56 78
30'
–
–
–
–
–
–
–
–
–
–
21 53 74
20 52 74
17
PERFORMANCE DATA – HOODS
Performance Data — 30°, 60° and 90° Downward Deflector Hoods — Blower Models
H
S
S
90° HOOD
Mounting
Height to
Bottom of
Heater
30° Downward Hood For Blower Units ➁
Model
BAE 50 BAE 75
BAE 100 BAE 125 BAE 145 BAE 175 BAE 200
BAE 225
BAE 250
BAE 300
BAE 350
BAE 400
X Y Z
X Y Z
X Y Z
X Y Z
X Y Z
X Y Z
X Y Z
X Y Z
X Y Z
X Y Z
X Y Z
X Y Z
8'
0 25 34
0 37 50
0 37 50
0 47 64
0 49 67
0 46 63
0 54 73
0 56 77
0 62 85
0 65 89
0 77 105
0 76 104
10'
0 22 30
0 35 48
0 35 48
0 45 62
0 48 66
0 45 61
0 53 72
0 55 75
0 61 83
0 64 88
0 76 103
0 75 103
12'
0 16 22
0 32 44
0 32 44
0 43 59
0 46 63
0 43 59
0 51 70
0 53 73
0 59 81
0 63 86
0 75 102
0 74 101
14'
–
0 29 40
0 29 40
0 41 56
0 44 60
0 40 55
0 49 67
0 52 70
0 58 79
0 61 84
0 73 100
0 73 100
16'
–
0 23 32
0 23 32
0 38 52
0 41 57
0 37 51
0 47 64
0 49 67
0 56 76
0 60 81
0 72 98
0 71 98
18'
–
–
–
0 34 47
0 38 52
0 33 45
0 43 60
0 46 64
0 53 73
0 57 78
0 70 96
0 70 95
20'
–
–
–
0 28 38
0 33 45
0 26 37
0 40 54
0 43 59
0 50 69
0 55 75
0 68 93
0 67 92
22'
–
–
–
–
0 24 34
–
0 34 47
0 38 53
0 47 64
0 51 71
0 65 90
0 65 89
24'
–
–
–
–
–
–
0 25 35
0 31 43
0 42 58
0 47 65
0 63 86
0 62 85
26'
–
–
–
–
–
–
–
–
0 36 50
0 42 58
0 59 81
0 59 81
28'
–
–
–
–
–
–
–
–
0 23 33
0 34 58
0 55 76
0 55 75
30'
–
–
–
–
–
–
–
–
–
–
0 50 69
0 49 68
32'
–
–
–
–
–
–
–
–
–
–
0 43 60
0 42 59
Mounting
Height to
Bottom of
Heater
60° Downward Hood For Blower Units ➁
Model
BAE 50
BAE 75 BAE 100 BAE 125 BAE 145 BAE 175 BAE 200 BAE 225 BAE 250
BAE 300
BAE 350
BAE 400
S
S
S
S
S
S
S
S
S
S
S
S
8'
24
38
41
55
60
58
71
75
86
96
121
124
10'
22
34
36
50
54
52
64
67
77
86
109
111
12'
20
31
33
45
49
47
58
61
71
79
99
101
14'
18
29
31
42
45
44
54
57
65
73
92
94
16'
17
27
29
39
42
41
50
53
61
68
86
88
18'
–
25
27
37
40
39
47
50
58
64
81
83
20'
–
24
26
35
38
37
45
48
55
61
77
78
22'
–
23
25
34
36
35
43
46
52
58
73
75
24'
–
–
–
32
35
33
41
44
50
56
70
72
26'
–
–
–
31
33
32
40
42
48
54
68
69
28'
–
–
–
30
32
31
38
40
46
52
65
66
30'
–
–
–
–
31
30
37
39
45
50
63
64
32'
–
–
–
–
–
–
36
38
43
48
61
62
34'
–
–
–
–
–
–
35
37
42
47
59
60
Mounting
Height to
Bottom of
Heater
90° Downward Hood For Blower Units ➁
➁
Data Based on unit fired at full rated input, 60°-80°F entering air temperature, and a 40°F temperature rise through unit.
Maximum mounting heights higher versus units without outlet devises.